Troubleshooting / Parts
To Reset all Parameters to Factory Defaults
1.
Turn off the power to VFD.
2.
Disconnect the STF/SD jumper at the STF end.
3.
Turn on the power to the VFD.
4.
Push 'PU/EXT' once. The PU light will go on,
and the 'EXT' light will go off.
5.
Push 'MODE' once to display Parameters.
6.
Turn the knob counterclockwise to 'All C'
('All Clear'). Push 'SET'.
7.
Change setting of 'All C' from '0' to '1' to reset
all parameters to their factory default settings.
Push 'SET'.
8.
Turn off the power to the VFD.
9.
Reconnect the STF/SD jumper.
10.
Turn on the power to the VFD.
To Display or Hide all Parameters beyond the user
Group Parameters
1.
Push 'MODE' once to display Parameters.
2.
Go to Parameter 160. Push Set.
3A. Change the setting from '9999' to '0'. Push 'SET'
to display all parameters.
3B. Change the setting from '0' to '9999'. Push 'SET'
to hide all parameters except the User Group
Parameters.
4.
Push 'MODE' twice to return to the Standard Display.
To Lock or unlock Parameter settings
1.
Push 'MODE' once to display Parameters.
2.
Go to Parameter 160. Push Set.
3.
Change the setting from '9999' to '0'. Push 'SET'
to display all parameters.
4.
Turn knob to P. 77. Push 'SET'.
5A. Change the setting from '2' to '1' to LOCK
settings. Push 'SET'. Go to Step 6.
5B. Change the setting from '1' to '2' to UNLOCK
settings. Push 'SET'. Go to Step 6.
6.
Return to P. 160. Push 'SET'.
7.
Change the setting from '0' to '9999'. Push 'SET'
to hide all parameters except the User Group
Parameters.
8.
Push 'MODE' twice to return to the Standard Display.
PENTEK Control LED Error Codes and
system Faults
Most faults will automatically reset, allowing the VFD to
automatically restart and continue normal operation.
If a fault does not reset, the drive will make 10 attempts
to restart the pump and will then go into a lockout
condition requiring manual reset.
If your VFD locks out, turn off the power to the VFD,
wait 60 seconds, and turn it back on. The VFD should
operate normally. If not, call your installer for assistance.
The faults listed below require a manual reset (that is,
they do not attempt to reset automatically). Follow the
indicated suggestions. If the error code won't clear,
call Pentair Customer Service at 1-866-973-6835.
REPaIR/aCCEssORy PaRTs LIsT
Part
Description
4-20 Milliamp, 0-100 psig Transducer
10' Shielded Transducer Cable
1/2" NPT Liquid Tight Cord Grip*#
1/2" Liquid Tight Conduit Connector
3/4" Liquid Tight Conduit Connector
Transducer Weather Boot*
25' Shielded Transducer Cable*
50' Shielded Transducer Cable*
100' Shielded Transducer Cable*
150' Shielded Transducer Cable*
200' Shielded Transducer Cable*
NOTE: Use the cable length appropriate to your installation.
* Purchase separately.
# Cable size 0.150"/0.250"
NEMA 3R Only
=
9
Part
Number
U17-1286R
U18-1593
U17-1337
*
U17-1284
=
=
*
U17-1285
U17-1338
U18-1594
U18-1595
U18-1596
U18-1597
U18-1598