Supplement to ProTool V6.0 + SP1
1.1
Validity
Applies to all TP 27 operating units with 6" and 10" displays in conjunction with
ProTool V6.0 and recipes modified using ProTool V6.0 on the above named
operating units.
1.2
Fault Description
If a TP 27 operating unit with a 6" or 10" display was in use and data records
were newly created or modified on the internal Flash using the firmware version
V6.0 (ProTool V6.0), the data was no longer legible (either immediately or
some time later).
1.3
Fault Elimination
Please carry out the following steps in order to clear this fault:
If a backup copy of the data record exists which was not created using the
firmware version V6.0, it is sufficient to read it in again following the installation
of ProTool V6.0 + SP1. It is immaterial whether the backup copy was made on
a memory module using the ProSave tool or the Backup/Restore function.
If upgrading to ProTool V6.0 + SP1 is carried out directly from a firmware
version older than V6.0 or no data record manipulations have been carried out
using firmware V6.0, the data records can continue to be used without any
restrictions.