DC Lithium UPS with DIN rail
□□□□□□□
RPS
1
2
3
4
1. Input and output voltage: 12, 24 (VDC)
2. Capacity: 30, 60 (W)
3. Enclosure type: DR – DIN rail
4. Battery type: L – Lithium-ion battery
1. Description
The RPS series is a DC lithium UPS with DIN rail ideal for providing
backup power in control panels. Suitable for distributed environments
in the industry 4.0.
It provides 24VDC continuous output voltage without interruption for a
load current of up to 1.25A. Being connected to the 24VDC power
supply at the input charges the battery. In the event of a power supply
fault, the RPS supplies power with the stored energy, ensuring
uninterrupted service for the connected devices.
6
7
1
8
2. Device Elements (Fig.1)
(1) External enclosure.
(2) Alarm relay block terminals.
(3) Power In Led indicator.
(4) Input and output block terminals.
(5) Air vents.
(6) Universal DIN rail adapter.
(7) DIN rail.
(8) ON/OFF button.
3. Safety notes and warning instructions
To ensure that the device can be operated safely and all functions can
be used, please read these instructions carefully.
Installation and startup must only be carried out by qualified personnel
following the country-specific regulations (e.g. VDE, DIN).
Safety precautions
Before installation:
Installation and connection:
5
4
3
2
For use:
4. Precautions for safe use
Once installed, connect the device to the power supply and press the
ON/OFF button. Charge the device before its use.
To uninstall, disconnect the device to the power supply and press the
ON/OFF button.
To store the device for a long time, make sure it is properly turned
OFF. The built-in battery discharges itself even if it is not used.
Make sure all cables are the correct size for the
maximum current flow of the device or have separate
fuse protection.
Ensure enough convection of air around.
Make sure input voltage is 24VDC ±10%. Connecting
a different voltage may result in malfunction or in
damage to the device, or cause a fire.
Make sure to connect only devices using 24VDC.
Overvoltage or overcurrent may damage the
connected devices.
When an unusual sound or smell occurs, stop the
supply of power and press ON/OFF button.
Do not disassemble, repair, or modify the unit. Doing
so may cause an electric shock or a fire.
Do not exceed the ranges specified for environmental
conditions during use/storage, it might cause damage
to the device or fire.
Do not install or store the unit in places:
Closed without ventilation.
Exposed to flammable or corrosive gas.
With high humidity.
With large amount of dust.
Exposed to direct sunlight.
Exposed to shock or vibrations.
Outdoors.
Include a easy to operate breaker between the power
supply and the device.
Do not block the air vents (upper and lower).
Recommended space of 50 mm or more above the
top and below the bottom each in order to avoid the
internal temperature to rise,which may cause the unit
to fail and the battery to deteriorate.
This device is able to supply electric power even when
the inner control circuit is damaged. Press the
ON/OFF button in order to disconnect the batteries.
If problems are found when charging, press the
ON/OFF button in order to disconnect the batteries.
5. Installation instructions
to improve the long time reliability of the device, pay attention to heat
dissipation. Ensure convection of air around the device.
1
2
(1) Place the device in a vertical position on the DIN rail.
(2) Slide the device down to secure it to the DIN rail.
(3) Press the device until the locking tab is engaged.
6. Uninstall instructions
2
1
(1) Slide the securing tab down with a screwdriver.
(2) Pull the device forward to disengage it from the DIN rail.
(3) Slide the device up to remove it from the DIN rail.
7. Conformance to EC Directives
This product complies with EC Directives. To ensure that the machine
or device in which the this product is used complies with EC
Directives, the product must be used as per this user manual.
Applicable directive: EMC Directive 2014/30/EU
Standards: EN 61000-6-2:2005, EN 61000-6-3:2007/A1:2011
Incorrect Method