Fault
Reason
Remedy
Does not switch
No power
Check power
Faulty signal line
Check signal line
Faulty electronic insert
Exchange
Strong build-up
Select suitable measuring
range setting (see Page 26-28)
FEW 54: contacts welded
Exchange FEW 54;
together (after short-circuit)
put fuse in contact circuit
Conductivity of liquid too low
Select different measuring
principle
Set correct mode at electronic
Switches
Min-/Max- fail-safe mode set
insert
incorrectly
wrongly
Mount device in a bypass
Faulty switching
Thick heavy foam,
if necessary
sporadic
very turbulent conditions,
foaming liquid
Extreme radio interference
Screen connecting cable
Clean cover and cable gland
Water in housing
and screw tight
Reduce load,
FEW 52: output overloaded
(cable) capacitance
Endress+Hauser
Recherche de défauts
Défaut
Ne commute pas Tension d'alimentation
Mauvaise
commutation
Mauvaise
commutation,
sporadique
36
Trouble-shooting
Cause
Mesure
Vérifier la tension
manquante
d'alimentation
Câble de signal défectueux
Vérifier le câble de signal
Electronique défectueuse
Remplacer
Colmatage important du
Sélectionner un réglage de
liquide trop faible
gamme approprié
(voir aussi pages 26-28)
FEW 54: contacts soudés
Remplacer FEW 54;
(après un court-circuit)
fusible dans le circuit courant
Conductivité du fluide trop
Sélectionner un autre principe
faible
de mesure
Sécurité min / max inversée
Régler correctement le circuit
de sécurité sur l'électronique
Mousse dense et lourde,
Monter le cas échéant
fortes turbulences,
l'appareil dans un bypass
liquide émulsionné
Parasites puissants
Blinder le câble de liaison
Eau dans le boîtier
Nettoyer le couvercle et les
entrées de câble et bien
revisser
FEW 52: surcharge de la sortie Réduire la charge et la
capacité (de ligne)
Endress+Hauser