UK Installation
It is possible to install only one insulation monitoring device for
each independent supply line. Fasten the device onto DIN rail
(35 mm) using a proper fixing system on the rear.
UK
Legend
A.
Auxiliary supply (rated voltage 115/230 V 50-60Hz)
B.
Error / Link Fail
C.
Insulating resistance and impedance measurement
D.
Output for remote signalling panels
E.
Serial output RS485 (only for ISOLTESTER-DIG-PLUS)
F.
Temperature sensor 2
G.
Temperature sensor 1
H.
Current transformer .../5 A input
I.
Programmable auxiliary relay output
Function
Network Address
Communication speed
Parity, bit data, bit stop
5
Adjustment
Indications
LED
SET
1÷255
2.40/4.80/9.60/19.2 SET
SET
N81/N82/E81/O81
UK Programming
Installation SETUP
Used to define the general functioning conditions
Button
12 + 11
13 / 12
13
13 + 12
Available settings from installation setup, (default values in
bold:)
Function
Delay for insulation alarm
Delay for impedance alarm
Config. temp. sensor T1
Config. temp. sensor T2
Delay for electrical overload off / 1÷60 sec
Transformation rate
Rated frequency
Fail safe (aux relay status)
Settings for serial output RS485 (only for ISOLTESTER-DIG-
PLUS)
Adjustment SETUP:
Display
To set threshold values and auxiliary relay activation mode
ID
Button Pressure
BDr
12
PAr
13 /
12
13
Available settings from adjustment setup, (default values in
bold:)
Function
Resistance threshold
Aux relay activation for low
resistance
Impedance threshold
Aux relay activation for low
impedance*
Aux relay activation for
Error / Link Fail*
Temp threshold T1/T2 (in
case of PT100)
Temp threshold T1/T2 (in
case of PTC)
Aux relay activation for
thermal overload T1/T2*
Current threshold
Aux relay activation for
electrical overload*
* Available only for ISOLTESTER-DIG-PLUS
Pressure
Function
continuous Access installation setup
quick
Adjust parameters
quick
Confirm parameter / next parameter
continuous Default values
Adjustment
1÷4 sec
off / 1÷4 sec
off/PTC/PT100
off/PTC/PT100
off/1 ÷ 40
50/60 Hz
NOP (open)
NCL (closed)
6
Function
continuous Access adjustment setup
quick
Adjust parameter
quick
Confirm parameter / next parameter
Adjustment
50÷500 kΩ
off/on
off/50÷500
kΩ
off/on
off/on
off / 30÷200
°C
off/on
off/on
off/0÷99.9
off/on
Indications
LED
Display
SET+R
DLY
SET+Z
DLY
SET+T1 nOD
SET+T2 nOD
SET+I
DLY
SET+I
Ct
SET
FrE
SET+Ou
SEt
tput
Relay
Indications
LED
Disp.
R
SEt
R+ Output
rEL
Relay
Z
Set
Z+ Output
rEL
Relay
Output Relay
rEL
+Link Fail
T1/T2
Set
T1/T2
rEL
T1/T2+
rEL
Output Relay
I
Set
T2+ Output
rEL
Relay