ALUBOX-EX
Ex tc = type of protection "tc" (with enclosures)
IIIC
= dust group
Dc
= EPL (Dust)
IP 66 = Degree of protection IP 66
3.2 PLATE EXAMPLE
Cod. 653.9001
S/N ????????
SCAME ATEX 01U
Ex nA IIC Gc
Ex tc IIIC Dc
IP66
Ts -20° C to +80° C
3.3 ENCLOSURE MATERIAL
Aluminium die-casting (oven-cured polyester resin finish, suitable for outdoor installations)
3.4 DEGREE OF PROTECTION
Degree of protection IP 66
3.5 SERVICE TEMPERATURE
The service temperature should be between -20 °C to +80 °C.Do not use the enclosure outside this temperature range.
3.6 LIMITATIONS OF USE
The products guarantee impact resistance performance required by the low mechanical risk standard condition
Equipment marked as a component: if the enclosure is intended to be used in a hazardous area, the user is
required to subject the entire unit to a 2014/34/EU type analysis, to be carried out by a Notified Body. Instructions
pertaining to installation, use and maintenance must always be included with the certified electrical device.
4. INSTALLATION
The installation must be carried out by qualified personnel pursuant to the relevant professional code (for
example, EN 60079-14), pursuant to national safety and accident-prevention rules and pursuant to this manual.
4.1 INSTRUCTIONS FOR SAFE USE
The IP degree of protection of the enclosure must maintained in the area of installation by using the following arrangement of cable
glands, plugs and gaskets as well as in compliance with installation standards. Should other certified components be assembled
in the enclosure, the user will have to take into consideration any limitations listed on the relevant certificates.
In case holes need to be drilled in the enclosures, use tools suited to the material the enclosure is made of (Aluminium die-casting)
and make sure you are using the proper drilling and feeding speed. The holes must fall within the drillable area defined for each
wall and must be carried out up to standard, without any burrs.
The thickness of the enclosure (min. 1 mm) DOES NOT allow the holes to be threaded.
These instructions presume that the necessary cable entries have been pre-drilled in the enclosure. The cable glands are usually
assembled during the installation.
The enclosure must be installed intact and free of any damage.
4.2 ACCESSORIES
Accessories must be assembled before the enclosure is installed and in accordance with the relevant instructions.
MP37122