Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

KA 1191
Application
With article KA 1191 it is possible to operate and balance the inlet water, and not on one way of the manifold. Furthermore
connecting to the KA 1191 to another manifold it is possible to operate the distribution both for the high temperature circuit and
for the radiant panels circuit with one single solution.
The high water temperature, coming from the boiler, enters the pump group GP 1190, through the lockshield of the kit for high KA
1191, while the relative outlet water is controlled by the thermostatic head placed on the thermostatic valve.
The lockshield regulates the max water flow entering the floor system, balancing the primary circuit.
The thermostatic head's task is that to keep the set temperature on the secondary circuit. When the temperature, detected by
the probe, changes on the secondary system, the thermostatic head assembled on the valve regulates the quantity of water to be
mixed until reaching the required temperature.
This type of system can supply a max thermal power of 20 kW with a Δt di 10 °C.

Technical data

Max temperature on the primary circuit
Temperature range on the secondary circuit
Max static pressure
Max differential pressure
Thermometer with housing
Connection to manifold
4
MANUAL INSTRUCTIONS
0 °C;
20 °C – 65 °C;
10 bar;
1 bar;
connection 1/2" with box Ø 65 mm;
G1" Male with 3 piece fitting with soft seal;
FIKA
Rev. 3.0 del 21/11/2018
EN

Publicidad

Tabla de contenido
loading

Tabla de contenido