Operation
Operation
Thank you for choosing a Testavit
|
Power socket tester with FI/RCD test (30 mA).
Power socket test
Using the Testavit
correct connection*, or for wiring errors.
The connection status is indicated by the LEDs and can be quickly
and clearly determined in the printed table.
To check to see whether an impermissible, high contact voltage is
applied at the protective earth connection, the finger contact must
be touched. if the LC display thereby illuminates, there is an error.
By activating the button "FI/RCD test" (< 3 sec.), a function check of
the residual current device (30 mA / 230 V AC) can be carried out.
Do the FI/RCD test only on fixed installations and con-
structions.
The test on movable and not fixed appliances, exten-
sions etc. could lead to a high current flow through the
protective earth connected metal parts.
This test does not replace the VDE 0100 tests on the FI / RCD cir-
cuit breakers!
®
Testboy
offers appropriate measuring devices.
In order to obtain a correct indication and to carry out the FI/RCD
test, the right phase must be applied. Thus, the instrument may
have to be rotated through 180° when checking a Schuko socket
(depending on the wiring).
* In many international standards it is specified that the phase at a
socket must be applied at the right connection (viewed from the front).
In Germany, there is no clear regulation for this, because the
Schuko plug is not protected against polarity reversal.
18
®
®
Schuki
1 LCD , sockets can be checked for
®
®
Schuki
1 LCD.
®
Testavit
®
Schuki
1 LCD