Aldes Smart Control
MODBUS CONNECTION
OJ-AIR2-HMI-35T is connected to the Aldes Smart Control
means of a Modbus cable. The Modbus cable can be connected
to the OJ-AIR2-HMI-35T by means of the RJ12 6P4C port or four
single-wire screw terminals. Whether the RJ12 6P4C port or screw
terminals are used does not influence the available functions or
operation.
Modbus RJ12 6P4C
Connect the Modbus cable to the Modbus port for a hand terminal
on the Aldes Smart Control
AIR2-HMI-35T (see fig. 5).
Modbus screw terminals
Connect the Modbus cable to the Modbus port for a hand terminal
on the Aldes Smart Control
nals on the OJ-AIR2-HMI-35T (see fig. 6).
RJ12
Screw terminals
1
+24 V
2
GND (earth)
3
Bus "B"
4
Bus "A"
5
+24 V
6
GND (earth)

TECHNICAL DATA

Supply voltage ........................................................24 V DC +/-10%
Cable dimensions ............................................. 10 x max. 0.75 mm²
Relative humidity ...................................... 0-95% (non-condensing)
Operating temperature .....................................................-10/+40°C
Enclosure rating .......................................................IP20 (EN 60529)
Port ........................................................................... 1 x RJ12 6P4C
......................................................................... 10 x screw terminals
Dimensions ............................................. 80x121x42 mm (see fig. 2)
Installation depth ................................................................... 22 mm
Max. power consumption .................................................... 900 mW
Standby power consumption ............................................. 600 mW
®
and to the RJ12 6P4C port on the OJ-
®
and to the corresponding screw termi-
®
English
by
®
13