iKX3232 – Interface compatible with KNX
TP1 Bus
Features:
Interfaces with TP1 Bus.
MdiBus interface.
DIN Rail Distribution Board mounting.
Applications:
Writing to 32 output groups.
Reading from 32 input groups.
Specifications:
Power supply Voltage: 15VDC;
Consumption: 30mA @ 15VDC;
TP Bus Voltage: 29VDC.
TP Bus consumption: < 3mA.
Storage Temperature: -10ºC to 60ºC;
Operating Temperature: 10ºC to 50ºC;
Maximum humidity: 80% non-condensing;
Physical Specifications:
Dimensions: 52mm x 90mm x 70mm, mounting on DIN rail (3
modules);
Protection degree: IP20, for indoor use;
Self-extinguishing plastic box UL-94 V0;
Compatibility:
Compatibility with iThink module: V1.0 or higher.
Compatibility with Mordomus software: Mordomus iThink
V2021.1 or higher.
ATTENTION:
Never open the housing.
Never remove the circuit board from its housing.
Never crimp or cut cables while they are connected
to powered equipment.
The module is not provided with additional protection
against short circuit, therefore it is recommended to
use a power supply with the correct specifications.
Mordomus shall not be liable for any damages
resulting from the use of our equipment outside the
specifications and/or for a purpose other than that
intended.
When using a low cross section cable there might be
voltage drops that could force the module into under-
voltage protection mode.
Do not connect power supplies with an output current
greater than 4A.
The power supply shall never be connected to the
modules at the extremities of the bus as in
The power supply shall be connected to a central
module in order to distribute the power to the
iKX3232
remaining modules. For larger installations add as
many power supplies as required, always respecting
a uniform distribution. View
Overview:
MdiBus In connector
MdiBus Out connector
Power Supply iPSE154 (15V 4A)
Addressing Button
Power supply connector 15VDC 2,1x5,5mm
TP Bus connector
Connections:
Specification and cross section of conductors:
MDiBus Circuit - CAT 6 UTP;
MDiBus connection: To connect the module to the MDiBus a CAT
6 UTP cable with RJ45 connectors according to EIA568A or
EIA568B standards must be used.
15VDC Power supply: It is recommended to use the iPSE154
power supply. The iKX3232 module can source its power from
other nearby modules through the MDiBus cable.
Enrollment:
To enroll the iKX3232 module proceed as follows:
1.
Make sure that the iKX3232 is powered by a suitable
power supply
and connected to the MdiBus
.
2.
In the Mordomus software access the menu
Configurations
and
Modules/Addresses.
3.
On the iKX3232, press and hold the addressing
button
for at least 1sec. The green LED will
blink slowly until the addressing is complete.
4.
The iKX3232 should be added automatically to the
list and the green LED should stop blinking.
Setting KNX group start address 0/0/x:
In the Mordomus software under Configurations ->
Modules/Addresses → Double click on the iKX3232 module to set
the last byte of the KNX group address. Valid addresses are [1-
224] and [0] as compatibility mode for the old iKX3232 addressing
figure
2.
scheme.
Note: by default the old addressing scheme [0] is used.
HW 1.0 - FW 1.08 or higher
In this addressing scheme the KNX input group addresses are
Figure
3.
attached to the Mordomus input addresses while the KNX output
group addresses start always at 1:
KNX group start address = 0
Mordomus address occupation = [17 – 80]
Mordomus
Type
Address
17
Output
48
Output
49
Input
80
Input
When choosing a KNX group start address between [1 - 224] this
group address will correspond to the first Mordomus address of the
iKX3232:
KNX group start address = 1
Mordomus address occupation = [17 – 80]
Mordomus
Type
Address
17
Output
48
Output
49
Input
80
Input
KNX group start address = 65
Mordomus address occupation = [81 – 144]
Mordomus
Type
Address
81
Output
112
Output
access
the
sub-menu
113
Input
144
Input
Data types that can be written to:
1.001 Switch
5.001 Percentage (0..100%)
Data types that can be read:
1.001 Switch
9.001 Value Temperature
Reset:
To perform a reset to the module, interrupt the 15VDC
power supply for 5 seconds.
LED codes:
Green LED ON: Module powered and enrolled to software;
Red LED ON: Module powered and not enrolled to software;
Green and Red LEDs blinking simultaneously: Under-voltage
protection mode. Power supply voltage is to low;
Green LED blinking continuously: Module awaiting address
definition;
Red LED flashing: Module sending/receiving data.
KNX Group Address
Note: The light of the green and red LEDs is visible through the
0/0/1
grid of the plastic enclosure.
0/0/32
0/0/49
0/0/80
RoHS
KNX Group Address
-----------------------------------Disclaimer---------------------------------------
This product is neither certified or approved by the KNX
0/0/1
association. All product names, logos, and brands are property of
their respective owners. The use of the term "KNX" is solely
0/0/32
intended
endorsement is implied.
0/0/33
http://mordomus.com/mordomus/docs/ithink/iKX3232.pdf
0/0/64
KNX Group Address
0/0/65
0/0/96
0/0/97
0/0/128
PT
iKX3232 – Interface compatível com Bus
KNX TP1
Caraterísticas:
Aplicações:
v.2120
This product complies with the Electromagnetic
Compatibility Directive 2014/30/EU.
This product conforms with the EU Directive 2011/65,
regarding the restriction of use of certain hazardous
substances in electric and electronic devices.
For EU countries only.
All old electrical and electronic devices must be
separated from normal household waste and disposed
of at designated facilities. For further information
contact your local authorities, waste disposal office or
the shop where you bought the device.
to
inform
about
certain
compatibilities
and
no
Interligação com barramento TP1.
Interface MdiBus;
Montagem em calha DIN.
Escrita para 32 grupos de saída.
Leitura de 32 grupos de entrada.
2/5

Publicidad

loading