7. I/O configuration
To configure the day/night function a different reference value will appear, depending on the established configuration.
If the input is not operative (NO) and the work mode is the CPC mode, the pressure value will be that configured
in PRESSURE REF 1. If the work mode established is min/max., the value will be that established in the
reference value as the minimum value.
If the input is operative (NC) and the work mode is the CPC mode, the pressure value will be that configured in
PRESSURE REF 2. If the work mode established is min/max., the value will be that established in the reference
value as the maximum value.
8. Software configuration
To improve the CPC configuration, the
equipment is supplied with PC software.
The Sodeca CPC Utility programme allows
the user to choose the port to which they want
to be connected, as the CPC enables the
configuration of the different CPC equipment
applications and parameters: constant flow
rate, with a constant pressure or with a
Maximum and a Minimum value. The text box
below the "show last logs" tab contains a text
box that displays the latest errors generated in
the equipment. An errors log can be obtained
by selecting the tab "show last logs". With a
log of the errors detected in the equipment.
If the equipment is not supplied through an electrical power source and the option exists
of supplying the electronic board through the PC. To do this, activate the "jumper J22" and the electronic board is supplied
with power through the USB port.
9. Configuration of the browser menus
Buttons A and C are used to change the configuration menu. To select the menu to be accessed, click on button B.
Once inside the configuration menu, a flashing value will appear. To increase the value use button C and to reduce it, use
button A. Once the new value has been defined, use button B to
set it and change the screen.
LCD DISPLAY
A
B
C
D
SW3
SW4
SW1
SW2
A: Back
B: Select
C: Forward
D: