Assembly and operating instructions Type 7E.36
65 A-active-energy meter, three-phase, Fig. 1 (2-tariff meter is illustrated)
Description
The 7E.36 is a space-saving, modern, electronic rotary
current meter, of accuracy class 1 (according to
EN 62053-21), class°B respectively (according to
EN 50470-1). The tamper-proof energy meter is fitted
with a high-quality counting mechanism and can be
mounted on a 35°mm rail regardless of location. The
counting mechanism is fitted with a reverse lock and can
be read at any time even without power supply.
External tariff switching is possible with the double
tariff meter.
Technical data
Connection
Fig. 2 (on the 1-tariff meter
■
diagram
connections E1°–°E2 are missing
for tariff-switching device
R°T1,°T2)
Dimensions
Fig. 3 (on the 1-tariff meter the
■
right-hand counter is missing)
Characteristics
3-phase, direct connection meter
■
Class 1 according to EN
■
62053-21, Class B according to
EN 50470-1
PTB approval (Germany) and MID
■
approval (EU and Switzerland)
SO+/SO- output with
■
100 Imp/kWh
Nominal currnt strength In = 10 A
■
Maximum current strength
■
I
max
Starting current Ist = 40 mA
■
Assembly
On 35mm rail (EN 60715TH35)
■
Counting mech.
0...999.999,9
■
capacity
Display
Mechanical, 4 mm figures,
■
decimal point red
Nominal voltage
3 x 230 VAC; 50 Hz; P< 0,4 W
■
per phase
LED function
flashing (red)
■
Normal operation 100 impulses/
■
kWh (impulse pause: 150 ms):
in kW = Number of impulses
per min x 0.6
4 319 5047 0b
06.2009
= 65 A
No consumption, no
impulses
Low consumption
High consumption
FINDER SpA
Via Drubiaglio, 14
10040 Almese (TO) - ITALY
Notes before connecting
1. Do not connect L1, L2 to L3 to N.
2. In order to avoid moisture in the meter due to
condensate build-up, acclimatise the meter at room
temperature for about half an hour before connecting.
Attention!
These devices must only be installed by a professional
electrician, otherwise there is the risk of fire or the risk
of an electric shock.
Assembly note:
The rotary current meter can be mounted onto bearing
rail (EN°60°715°TH35). It may only be installed and
used in installation cupboards with protection type IP 51
(protected against penetrating dust and dripping water).
EC declaration of conformity
Finder SpA declares at its own responsibility:
The following energy meters are in compliance:
7E.36.8.400.0000
●
7E.36.8.400.0010
●
7E.36.8.400.0002
●
7E.36.8.400.0012
●
The following energy meters are approved for energy
billing:
7E.36.8.400.0010
●
7E.36.8.400.0012
●
Additionally they meet the following standards or
normative documents:
EN 50470 parts 1 and 3 (electronic meters)
●
Directive 2004/22/EC (MID) of the European
●
Parliament and Council on measuring devices
Appendix I, basic requirements
●
Appendix MI-003, electricity meters for kilowatt
●
hours
For year of issue of declaration of conformity according
to Directive 2004/22/EC see printed text on the
device.
Example: Declaration of conformity for 2007
Error LED (Phase missing or connection inverted)
3 s
3 s
3 s
3 s
3 s
3 s
3 s
3 s
3 s
3 s
3 s
3 s
3 s
3 s
3 s
3 s
3 s
3 s
Subject to change without notice
English
(1 tariffs)
(1 tariffs)
(2 tariffs)
(2 tariffs)
(1 tariffs)
(2 tariffs)
L1 not connected
L2 not connected
L3 not connected
L1 und L2 swapped
L1 and L3 swapped
L1, L2 + L3 swapped /