ELKO EP, s.r.o.
Palackého 493
769 01 Holešov, Všetuly
Czech Republic
Tel.: +420 573 514 211
e-mail: elko@elkoep.com
www.elkoep.com
Made in Czech Republic
02-79/2016 Rev.: 1
Characteristics
• cycler with independent adjustable switch ON/OFF
• it is used for regular room ventilation, cyclic dehumidifi cation, light control,
circulating pumps, noon signs, etc.
• 2 time functions:
1) Cycler beginning with pulse
2) Cycler beginning with pause
• function choice is done by an external jumper of terminals S-A1
• time scale 0.1 s - 100 days devided into 10 time ranges
(0.1 s - 1 s / 1 s - 10 s / 0.1 min - 1 min / 1 min - 10 min / 0.1 hrs - 1 h / 1 hrs - 10 hrs /
0.1 day - 1 day / 1 day - 10 days / 3 days - 30 days / 10 days - 100 days)
• rough time setting via rotary switch
• supply voltage: AC 230 V or AC/DC 12 - 240 V
• output contact: 1x changeover / SPDT 16 A
• output indication: multifunction red LED
• 1-MODULE, DIN rail mounting
Description
4
5
6
7
8
9
cos φ ≥ 0.95
Type of load
AC1
Mat. contacts AgNi,
contact 16 A
250V / 16A
Type of load
AC13
Mat. contacts AgNi,
contact 16 A
250V / 6A
1. Supply terminals
1
2. Terminal for function selection
2
3. Output indication
3
- fast blinking - switched output 15-18; t1
- slowly blinking - switched output 15-16; t2
4. Supply indication
5. Rought time setting - IMPULSE (time setting
in range 0.1 s .. 100 days)
6. Fine time setting - IMPULSE (fl uent setting
of rough range)
7. Rought time setting - PAUSE (time setting in
range 0.1 s .. 100 days)
8. Fine time setting - PAUSE (fl uent setting of
rough range)
9. Output contact
M
M
AC2
AC3
uncompensated
250V / 5A
250V / 3A
230V / 3A (690VA)
K
AC14
AC15
250V / 6A
250V / 6A
CRM-2H
Assymmetric cycler
Symbol
Connection
Cycler beginning with
pulse
+
A1 S A2
15 16 18
AC5a
AC5a
compensated
x
M
DC3
DC1
24V / 6A
24V / 16A
1 / 2
A1
16 18
S
A2
15
Cycler beginning with pause
Un
- -
HAL.230V
AC5b
AC6a
800W
x
250V / 3A
M
DC5
DC12
24V / 4A
24V / 16A
EN
(jumper S-A1)
Un
+
-
A1 S A2
15 16 18
AC7b
AC12
250V / 10A
DC13
DC14
24V / 2A
24V / 2A