WARNING
Read all safety warnings, instructions, illustrations
and specifications provided with this product.
Failure to follow all instructions listed below may
result in electric shock, fire and/or serious injury.
Save all warnings and instructions for future
reference.
Safety notes
Operating voltage 230 V AC!
Risk of injury from electric shock!
Do not reverse L+N! Connect PE!
The BSY+ bus also operates with 230V!
- Connection has to be carried out only by an
authorized electrical specialist
- Danger of violent pressure in handaccessible area
- Keep away People from the operating area of the
drive
- Keep away children from the control
- Observe pressure load diagram of the chain!
- Use only in dry rooms
- Only for inside mounting.
Use rain detector with danger of rain
(e.g. at domelights or roof windows)
- Just use unchanged original D+H parts
- Observe mounting instructions of bracket set!
Observe enclosed r ed safety slip!
Functional description
A synchron-group (CDP-K-BSY+) can be count up to
8 drives, which communicate by a bus. Each drive
has it's own adress. This adress is configurable with
software SCS.
The last drive of a synchron-group is the master,
which controls the other drives, the slaves. Different
forces between the drives of a group will balanced
with intelligent force- and position control. In case of
malfunction respective cutoff of a drive or a position
difference > 30 mm, all drives will shut down from the
master-drive.
6/24
CDP-K-BSY+
Intended use
- Chain drive for electric opening and closing of heavy
windows and flaps in the facade and roof area
- Operating voltage 230 V AC
- Useable for smoke ventilation, D+H Euro-SHEV
according to DIN EN 12101-2 as well as
daily natural ventilation
- Only for inside mounting
Performance features
- Micro processor controlled synchro electronics
BSY + for a precise synchronous run of up to
4 drives
- Individually programmable (via software SCS)
- SHEV-high speed function (fast-running
feature in OPEN-direction)
- Protection system for the main closing edge
- Locking relief after closing
- Especially quiet motor running in ventilation mode
- Symmetrical chain outlet
- Connection via pin-and-socket connector
- Optinal with "-AS2" = protection class 2 and
"-AS3" as well as "-LS" = protection class 3
Extent of supply
Drive unit with 2,5 m silicone cable. Dependent on
the type of window, different bracket sets are
available separately.
Pressure load diagram
Observe maximum pressure load of the chain!
Maximum pressure load of the chain is not
automatically identical with maximum pressure force
of the drive!
2000
1500
1000
500
0
English
Stroke / (mm)
99.825.46 1.2/11/15