Technical Data
Input
•
Nominal voltage:
115/230 VAC auto select
Power factor (PFC):
as required to meet EN61000-3-2
Output
•
Nominal voltage:
24V (22.5-28.5VDC Adj.)
•
Power boost:
2x nominal current for 2 sec.
(except for SDN 4-24-100P)
•
Holdup time:
> 20ms at Full Load (25˚C)
•
< ±2 % overall
Tolerance:
Line regulation
<0.5%
Load regulation
<0.5%
Time & temp. drift
<1%
•
24.5V ± 1%
Initial voltage setting:
•
Ripple:
< 50mVpp
•
Power back immunity:
> 35V
•
Parallel Operation:
Jumper Selectable Via Front Panel
•
Over voltage protection:
< 33VDC
Standards, Certifications
EMC
Emissions
EN 61000-6-3, Class B EN55011, EN55022 Radiated
Conducted including Annex A
Immunity
EN 61000-6-2, EN61000-4-2 Level 4, EN61000-4-3 Level 3,
EN61000-4-6 Level 3, EN61000-4-4 Level 4 input and level 3
output. EN61000-4-5 Isolation class 4, EN61000-4-11, Tr
protection according to VDE 0160/W2 over entire load range.
Approvals
EN60950, UL508 Listed, cULus, UL 60950, cURus, CE (LVD 73/23
& 93/68/EEC), (EMC 89/336 & 93/68/EEC). EN61000-3-2, EN60079-
15 (Class 1, Division 2 hazardous location, Groups A, B, C, D w/ T3
temp class up to
60
˚C Ambient.),
CENELEC ATEX EEx nC IIC T3 II 3 G, SEMIF47, Sag Immunity,
SDN 2.5 & 4 – UL60950 testing to include approv
power supply acc. To NFPA 70 art. 725-41 (a)(2).
Environmental Data
Ambient temperature
•
Storage/Shipment
-25˚C...+85˚C
•
Full nominal load
-10˚C...+60˚C
•
Derated
+60˚C...+70˚C
Degree of protection: IP20 (EN6052 , Protect the unit from moisture (and
9)
condensation)
Installation
Fusing
Input
Internally fused.
Output
Outputs are capable of providing high currents for short periods of
time for inductive load startup or switching.
Mounting
Simple snap-on to DIN TS35/7.5 or TS35/15 rail system. Unit
should handle normal shock and vibration of industrial use and
transportation without falling off the rail.
Connections
Input: screw terminals, connector size range: 16-10AWG (1.5-
6mm2) for solid conductors.
Output: Two terminals per output, connector size range: 16-10AWG
(1.5-6mm2) for solid conductors.
This equipment is suitable for use in Class 1, Division 2, Groups A,B,C,D or non-hazardous
locations only
WARNING – EXPLOSION HAZARD – Substitution of components may impair suitability for
Class 1, Division 2.
WARNING – EXPLOSION HAZARD – Do not disconnect equipment unless power has been
switched off or the area is known to be non-hazardous.
DIN Rail Mounting
Snap on the DIN Rail:
1. Tilt unit as
illustrated
2. Put it onto the DIN
Rail
3. Push downwards
until stopped
4. Push at the lower
front edge to lock
ansien
t
5.
Shake the unit
slightly to ensure
that the unit is
secure
al
as NEC Class 2
SDN Series
Power Supplies
SDN 2.5-24-100P
SDN 4-24-100LP
SDN 5-24-100P
SDN 10-24-100P
Rev. 6/10/2005
Montaje en Riel DIN
Montage du Rail DIN
Atorar en en Riel DIN:
Poser le Rail DIN:
1. Incline la unidad
1. Incliner l'appareil
como se ilustra
comme illustré
2. Póngala sobre el Riel
2. Encliqueter sur le
DIN
Rail DIN
3. Empuje hacia abajo
3. Pousser vers le bas
hasta que se
jusqu'à l'arrêt
detenga
4. Appuyer sur le bord
4. Empuje de la parte
inférieur pour fixer
baja del frente para
asegurar
5.
Vérifier que l'appareil
est bien fixé
5.
Mueva la unidad
ligeramente para
verificar está segura
Technical Services
USA
(800) 377-4384
International
(847) 679-7800
www.solaheviduty.com