Function settings (continued)
No.63
External fan speed input setting (0 - 10 VDC)
Set external fan speed input setting.
DIP-SW
PZ-61DR-E
Setting
check
SW No.
Setting
Function No. Setting Data
-
-
2-3 OFF
2-6 OFF
(Factory setting)
SW2-3
2-3 ON
63
SW2-6
2-6 OFF
2-3 OFF
2-6 ON
2-3 ON
2-6 ON
Lossnay changes fan speed according to input voltage to CN26.
When pattern X or Y is selected, it is not possible to change fan
speed from remote controllers.
(External input has higher priority)
[Pattern X]
When the input voltage is more than 6.0 VDC, Lossnay operates at
fan speed 4 (maximum air volume). Lower voltage than 6.0 VDC,
Lossnay operate at weaker fan speed. (Connection example: if you
use a CO
sensor which 0 - 10 VDC equals to 0 - 2000 ppm, 6.0
2
VDC equals to 1200 ppm)
[Pattern Y]
When the input voltage is more than 5.0 VDC, Lossnay operates at
fan speed 4 (maximum air volume). Lower voltage than 5.0 VDC,
Lossnay operate at weaker fan speed. (Connection example,:if you
use a CO
sensor which 0 - 10 VDC equals to 0 -2000 ppm, 5.0
2
VDC equals to 1000 ppm)
[Pattern Z]
Lossnay changes fan speed as the table below. (Connection
example: BMS (Building Management System))
Input voltage[VDC] Fan speed
0 - 1.0
-
1.5 - 2.5
1
3.5 - 4.5
2
5.5 - 7
3
8.5 - 10
4
When the input voltage is in-between, it will cause unstable operation.
No.100
Initialization
Set to initialize the remote PZ-61DR-E setting.
All settings which are changed by users are cancelled.
DIP-SW
PZ-61DR-E
Setting
check
SW No.
Setting
Function No. Setting Data
-
-
N/A
100
-
-
Setting
External fan speed
check
control using CN26
0
DIP-SW priority
(Factory setting)
External fan speed
1
control is N/A.
2
Refer to pattern X
3
Refer to pattern Y
4
Refer to pattern Z
Fan speed changing from
Remote controller
Available
Not available
Not available
Not available
Not available
Setting
Initialization
check
0
N/A
1
Available
Eng-21