Descargar Imprimir esta página

Galletti MYCOMFORT MEDIUM Manual Del Usuario página 26

Mando lcd para terminales

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 54
MYCOMFORT MEDIUM
DEHUMIDIFICATION
WATER CONTROL
If enabling conditions do not exist, the dehumidification function will be
temporarily inhibited.
The same will occur in the event that the probe is disconnected.
NB: once the target level of humidity is reached or the controller is switched
off, the dehumidify option will be unselected
G B
DISPLAY
The display shows the following information:
> Dehumidify ON: symbol lit
> Dehumidification temporarily inhibited: flashing symbol
ALARMS
This control governs two types of alarms:
> Serious Alarms: cause the forced switching off of the thermostat
> Non-serious Alarms: do not cause the forced switching off of the ther-
mostat, but disable possible critical functions
SERIOUS ALARMS
Alarm code
> Code 01 = error of external air temperature sensor (in case of on-board
thermostat)
> Code 02 = error of internal air temperature sensor (in case of wall mounted
thermostat and disconnected external air temperature sensor)
NON-SERIOUS ALARMS
Thermostat OFF
> Code 03 =water sensor error
> Code 04 = external humidity probe error (only if a remote temperature
probe is installed)
> Code 05 = internal humidity probe error
NB: the alarm code is displayed only when the thermostat is switched off
FC66002605 - rev. 02
È severamente vietata la riproduzione anche parziale di questo manuale / All copying, even partial, of this manual is strictly forbidden
MODBUS
The protocol implemented in the controller is Modbus RTU (9600, N, 8, 2) on
RS485
FUNCTIONS IMPLEMENTED
> 0x03 : Read Holding Registers
> 0x04 : Read Input Registers
> 0x10 : Write Multiple registers
EXCEPTIONS IMPLEMENTED
Exception Code 02: Invalidate data address
LIST OF SUPERVISION PARAMETERS
DESCRIPTION OF READ-ONLY REGISTERS [R]
> "Staus" "REGISTER"
Bit 15
-
Bit 7
Vh
-
On/Off: unit status (0: Off, 1=On)
-
S/W: operation mode (0: S=cooling,1:W=heating)
-
P01: "on unit/wall-mounted" parameter
-
Eco: Economy logic active
-
Min.T: Minimum Temperature logic selected
-
Alarm: general alarm indication (activated when any of the managed
alarms is triggered)
-
Vc: status of digital output Vc
-
Vh: status of digital output Vh
-
DI1: logical value of dig. input 1 (the physical status of the input depends
on the associated logic)
-
DI2: logical value of dig. input 2 (the physical status of the input depends
on the associated logic)
Thermostat ON
-
P07: "DIN 2 Logic" parameter
-
P06: "DIN 1 Logic" parameter
-
Dehum: dehumidification ON (0:no, 1:yes)
-
P04: "water probe present" parameter
26
ADDRESS
REGISTER
0
Status
1
Speeds
2
Air temperature
3
Humidity
4
Water temperature
5
P00: Configuration
6
P05: Config. DIN
7
T. Active setpoint
8
T. User setpoint
9
LCD version
50
Digital 1
51
-
52
Setpoint - Cooling
53
Setpoint - Heating
54
Minimum Setpoint – Cool. R/W
55
Maximum Setpoint – Cool R/W
56
Minimum Setpoint – Heat. R/W
57
Maximum Setpoint – Heat R/W
58
Speeds
59
Economy Correction
H
Bit 14
Bit 13
Bit 12
Bit 11
-
P04
Deum
P06
L
Bit 6
Bit 5
Bit 4
Bit 3
Vc
Alarm
MinT
Eco
TYPE
U.M.
R
-
R
-
R
[°C/10]
R
%
R
[°C/10]
R
-
R
-
R
[°C/10]
R
[°C/10]
R
-
R/W
-
R/W
-
R/W
[°C/10]
R/W
[°C/10]
[°C/10]
[°C/10]
[°C/10]
[°C/10]
R/W
-
R/W
[°C/10]
Bit 10
Bit 9
Bit 8
P07
DI2
DI1
Bit 2
Bit 1
Bit 0
P01
S/W
On/Off

Publicidad

loading