Instruction Leaflet IL04020001E
Effective September 2013
Quick Start Parameter Guide
Predefined Application Parameters from Parameter P1.2
Parameter
Basic
(PNU)
(Standard Drive)
P1.1
1 = Only quick configuration
parameters
P1.2
0 = Basic
P1.3
1 = N/A
P6.1
1 = Control signal terminals (I/O)
(I/O)
P6.2
3 = AI1 (analog setpoint 1)
P6.3
00.00 Hz
P6.4
60.00 Hz
P6.5
3.0s
P6.6
3.0s
P6.7
0 = Ramp (acceleration)
P6.8
0 = Free coasting
P7.1
I
e
P7.3
1720 RPM
P7.4
0.85
P7.5
230/460/575V
1
P7.6
60 Hz
P11.7
0 = Deactivated
M1.1
0.00 Hz
1
230V = MMX11_, MMX12_, MMX32_.
400V = MMX34_, 575V = MMX35_.
This parameter will default based on style of unit.

Technical Support Contact Information

Americas
Website
www.eaton.com/m-max
Email
VFDaftermarketEG@eaton.com
Phone
1-877-386-2273 (8:00 a.m. to 6:00 p.m.
Eastern Time U.S. [UTC–5])
800-543-7038 (6:00 p.m. to 8:00 a.m.
Eastern Time U.S. [UTC–5])
Pump Drive
Fan Drive
1 = Only quick configuration
1 = Only quick configuration
parameters
parameters
1 = Pump drive
2 = Fan drive
1 = N/A
1 = N/A
1 = Control signal terminals (I/O)
1 = Control signal terminals (I/O)
(I/O)
(I/O)
3 = AI1 (analog setpoint 1)
3 = AI1 (analog setpoint 1)
20.00 Hz
20.00 Hz
60.00 Hz
60.00 Hz
5.0s
20.0s
5.0s
20.0s
0 = Ramp (acceleration)
0 = Ramp (acceleration)
1 = Deceleration time (ramp)
0 = Free coasting
I
I
e
1720 RPM
1720 RPM
0.85
0.85
230/460/575V
1
230/460/575V
60 Hz
60 Hz
0 = Deactivated
0 = Deactivated
0.00 Hz
0.00 Hz
EMEA
APAC
www.eaton.eu/electrical
www.eaton.com.cn/electrical
AfterSalesEGBonn@eaton.com
CustomerServicePDCNA@eaton.com
+49 (0) 180 5 223822
800 9881203
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
© 2013 Eaton
All Rights Reserved
Printed in USA
Publication No. IL04020001E / Z14231
September 2013
High Load
1 = Only quick configuration
parameters
3 = Hoisting device (high load)
1 = N/A
1 = Control signal terminals (I/O)
(I/O)
3 = AI1 (analog setpoint 1)
00.00 Hz
60.00 Hz
1.0s
1.0s
0 = Ramp (acceleration)
0 = Free coasting
I
e
e
1720 RPM
0.85
1
230/460/575V
60 Hz
1 = Enabled
0.00 Hz
M-Max Series
Adjustable Frequency Drives
Designation
Quick start parameters
Application
Country specific default settings
Primary remote control source
Primary remote speed reference
Minimum frequency
Maximum frequency
Acceleration time (acc1)
Deceleration time (dec1)
Start function
Stop function
Motor, rated current
Motor, rated speed (RPM)
Motor, power factor (cos w )
1
Motor, rated operating voltage
Motor, rated frequency
Torque increase
Output frequency (display only)