Finder 80.01.0.240.0000 Manual De Instrucciones página 2

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 6
80.01.0.240.0000
(12...240) V AC (50/60 Hz) / DC
U
: 10.8 V AC / DC
min
U
: 265 V AC / DC
www.findernet.com
max
1 CO (SPDT)
80.01
16 A 250 V AC
AC1
4000 VA
AC15
(230 V AC)
M
0,55 KW
(230 V AC)
(–10...+50)°C
IP 20
1
A
B
C
D
88.8 mm
2
3
3a
750 VA
3b
60.8 mm
17.5 mm
3c
3d
3e
• Open Type Device
• Pollution degree 2 Installation Environment
• Maximum Surrounding Air Temperature 40°C
• Use 60/75°C copper (Cu) conductor only and
wire ranges No. 14–18 AWG, stranded or solid
• Terminal tightening torque of 7.1 Ib.in. (0.8 Nm)
ENGLISH
80.01 MODULAR TIMER, MULTI-FUNCTION
1
FRONT VIEW
A = Time scales rotary selector
B = Time setting
C = LED
D = Functions rotary selector
2
TIME SCALES
3
WIRING DIAGRAM AND FUNCTIONS
(WARNING: the functions must be set before energising the timer)
3a
Without signal START functions:
Start via contact in supply line (A1)
AI = ON delay
DI = ON pulse
SW = Symmetrical recycling: ON start
3b
External START functions:
Start via contact into control terminal (B1)
BE = Signal OFF delay
CE = Signal ON and OFF delay
DE = Signal ON pulse
3c
Possible to control an external load, such as another relay coil
or timer, connected to the signal start terminal B1.
3d
With DC supply, positive polarity has to be connected to B1
terminal (according to EN 60204-1).
3e
A voltage other than the supply voltage can be applied to the
command Start (B1), example:
A1- A2 = 230 V AC
B1- A2 = 12 V DC
OTHER DATA
Minimum control impulse: 50 ms.
Recovery time: ≤ 50 ms.
35 mm rail mount (EN 60715).
WORKING CONDITIONS
In conformity with the European Directive on EMC (89/336/EEC), the
timer relay has a level of immunity, against radiated and conducted
disturbances, considerably higher than requirements of EN 61812-1
standard. However, devices like transformers, motors, contactors,
switches and power cables may cause disturbances and even damage
the timer electronic circuit. For that reason, the wiring cables must
be as short as possible, and, when necessary, the timer shall be
protected by the relevant RC network, varistor or surge voltage
protector.