Instruction Leaflet IL040029EN
Effective December 2017
North America cable and fuse sizes—525 Vac to 600 Vac ratings
575 V input
Frame size
Amp suffix
current (VT/I
FR1
4D5
4.2
7D5
7
010
9.3
FR2
013
12.5
018
16.7
022
20.4
FR3
027
25.2
034
31.7
041
38.2
FR4
052
48.1
062
57.4
080
73
FR5
100
91.3
125
114.1
144
132.9
FR6
208
202.8
250
243.8
Notes
Line and motor cable size is selected according to UL 508C Table 40.3 for copper conductor rated 75 °C. Use only with copper wire rated 75 °C here.
Size requirements for other different wire types are defined in the National Electrical Code, ANSI/NFPA 70.
Earthing conductor size is determined by the maximum overcurrent device rating used ahead of the drive according to UL 508C Table 6.4.
If power cubes or bypass are used, a UL listed Class RK5, J, T or equivalent fuse is recommended.
EATON
18
www.eaton.com
NEC motor amp
Current (VT/I
)
rating at 575 V
at 40 °C
L
3.9
4.5
6.1
7.5
9
10
11
13.5
17
18
22
22
27
27
32
34
41
41
52
52
62
62
77
80
99
100
125
125
144
144
192
208
242
250
NEC wire
Size (AWG)
)
Recommended
Line and
L
fuse rating
motor
10
14
10
14
15
14
20
12
30
10
35
10
40
6
45
6
50
6
70
4
80
4
125
2
150
1/0
175
2/0
200
3/0
400
2*1/0
400
2*2/0
PowerXL DH1 Series VFD
Terminal connection size (AWG)
Ground
Line and motor
14
26–10
12
26–10
10
26–10
10
20–6
10
20–6
8
20–6
8
6–2
8
6–2
6
6–2
6
6–1/0
6
6–1/0
4
6–1/0
4
1/0–350 kcmil
4
1/0–350 kcmil
4
1/0–350 kcmil
3
2*(1/0–300 kcmil)
3
2*(1/0–300 kcmil)
Ground
18–10
18–10
18–10
12–6
12–6
12–6
14–4
14–4
14–4
10–1/0
10–1/0
10–1/0
8–250 kcmil
8–250 kcmil
8–250 kcmil
3–300 kcmil
3–300 kcmil