Active Interface Module Chassis Liquid Cooled
Notes regarding the manual
Supplemental sheet / description
Note
Before installation in the cabinet, the transport plate below the filter module must be
removed.
2.4.7 Connecting the cooling circuit
In order to take into account local situations, the non-assembled connecting hose is provided in the
supplementary pack.
The hose connections should be attached using two hose clamps with a tightening torque of 3 Nm.
Straight connections are provided for P1, P3, P4 and P5.
An angled connection is provided for P7.
After assembly, a pressure test should be performed to ensure that there are no leaks.
2.4.9 Technical data
To take into account tolerances in the water circuit, for the Active Interface Module, the coolant circuit should
be dimensioned for 15 l.
2.4.9 Parameterization
The temperature monitoring thresholds must be correctly parameterized to ensure safe reliable operation:
Alarm threshold p3667 = 75 °C
Shutdown threshold p3668 = 80 °C