Descargar Imprimir esta página

Hubbell homeSELECT RFSQ2F Manual De Instrucciones

Publicidad

Enlaces rápidos

Quiet Fan-Speed Controls
RFSQ2F, RSFSQF
Rated at 120 V~ 60 Hz 1.5 A
Important Notes
Please read before installing.
1. CAUTION: Use control with a ceiling paddle fan only. Use only one ceiling paddle
fan per control. To avoid overheating and possible damage to other equipment, do
not use to control receptacles, fluorescent lighting fixtures, or transformer-supplied
appliances.
2. Controls require separate wires in the wallbox for fan and light. Do not use control
with a fan and light that operate with the same switch.
3. Set multi-speed fans to their highest setting before installing control.
4. Do not wire control in a circuit with a GFCI breaker/receptacle.
5. Install in accordance with all national and local electrical codes.
6. When no "grounding means" exist within the wallbox then the NEC
404-9 allows a control without a grounding connection to be installed as a
replacement, as long as a plastic, noncombustible wallplate is used. For this type of
installation, cap or remove the green ground wire on the control and use an
appropriate wallplate.
7. For new installations, install a test switch before installing the control.
8. Protect control from dust and dirt when painting or spackling.
9. It is normal for the control to feel warm to the touch during operation.
10. Clean control with a soft damp cloth only. Do not use any chemical cleaners.
Multigang Installations
When installing more than one control in the same wallbox, it may be necessary to
remove all inner side sections prior to wiring (see diagram). If pre-installed, remove the
wallplate and wallplate adapter from control. Using pliers, bend side section up and
down until it breaks off. Repeat for each side section to be removed. Note: No derating
required if ganged.
Each Control Has Inside
Sections Removed
This product may be covered by one or more of the following U.S. patents: 4,835,343; 4,835,816; 5,191,971; and
corresponding foreign patents. NEC is a registered trademark of the National Fire Protection Association, Quincy,
Massachusetts.
Installation
1 1
Turning OFF Power.
• Turn power OFF at circuit breaker (or remove fuse).
2 2
Removing Wallplate and Switch.
• Remove wallplate and switch mounting screws.
• Carefully remove switch from wall (do not remove wires).
Caution: Verify
power is OFF to
switch before
proceeding.
3 3
Verify Application.
• Switch must have two insulated wires connected to two screws and may
have a bare copper or green wire connected to a green screw. Note: Do
not connect to a light fixture.
Ground (Bare Copper
or Green Wire)
Hubbell Incorporated (Delaware)
185 Plains Road
Milford, CT 06461-2420
(203) 882-4800
English
4 4
Disconnecting Switch Wires.
Important Note: Your wall switch may have two wires attached to the same screw (see
illustrations below for examples). Tape these two wires together before disconnecting.
Connect both wires to the control wire in Step 5.
One wire in the
backwired hole and
one to the screw.
Screw Terminals:
Turn screws to loosen.
Important Wiring Information
2005, Article
®
When making wire connections, follow the recommended strip lengths and combinations for the
supplied wire connectors. Note: Wire connectors provided are suitable for copper wire only. For
aluminum wire, consult an electrician.
Small:
Strip insulation 3/8" (10 mm) for 14 AWG wire
Strip insulation 1/2" (13 mm) for 16 or 18 AWG wire
Use to join one 14 AWG supply wire with one 16 or
18 AWG control wire.
Large:
Strip insulation 1/2" (13 mm) for 10, 12, or 14 AWG
wire
Strip insulation 5/8" (16 mm) for 16 or 18 AWG wire
Use to join one or two 12 or 14 AWG supply wires
with one 10, 12, 14, 16, or 18 AWG control wire.
5 5
Wiring the Control.
• For installations involving more than one control in a wallbox, refer to the
section on Multigang Installations before beginning.
Note: Wire location will vary by product. Reference wires by color, not
location.
Do Not Remove
Outside Sections
Black
Middle Control Has Two
Green
Side Sections Removed
Black
120 V~
Green
60 Hz
Ground
6 6
Mounting Control to Wallbox.
• Form wires carefully into the wallbox, mount and align control.
• Install wallplate.
Start screws.
7 7
Turning ON Power.
• Turn power ON at circuit breaker (or replace fuse).
Operation
Medium
High
Low
Off
Off
RFSQ2F
One continuous wire
to the screw.
Push-in Terminals:
Looped Wire:
Insert screwdriver. Pull
Turn screw to loosen.
wire out.
Twist wire connector
tight.
Be sure no bare wire
is exposed.
Large
Small
• Connect the green control ground
wire to the bare copper or green
ground wire in the wallbox. (See
Important Note 6.)
• Connect one of the black control
wires to either of the wires removed
from the switch.
• Connect the remaining black control
wire to the other wire removed from
Ground
the switch.
Black
Fan
Align control and
tighten screws.
High
Med.
Low
Off
RSFSQF
037-106
Made and printed in the U.S.A.
8/06 P/N 037-106 Rev. A
Commandes silencieuses de
ventilateur à vitesses
RFSQ2F, RSFSQF
Puissance nominale de 120 V~ 60 Hz 1,5 A
Remarques importantes
Veuillez lire avant de procéder à l'installation.
1. MISE EN GARDE : Utiliser une commande avec un ventilateur de plafond à pales
seulement. Utiliser seulement un ventilateur de plafond à pales par commande. Pour
éviter la surchauffe et d'éventuels dommages à d'autres équipements, ne pas utiliser
ce dispositif pour commander l'intensité des prises de courant, des luminaires à
tube fluorescent, ou des appareils alimentés par transformateur.
2. Ne pas utiliser les commandes pour un ventilateur et une lumière qui fonctionnent
sur le même interrupteur.
3. Régler les ventilateurs à vitesses multiples sur la plus haute vitesse avant de
procéder à l'installation des commandes.
4. Ne pas raccorder les commandes à un circuit doté d'un disjoncteur/d'une prise
contre masse défectueuse (GFCI).
5. L'installer en respectant tous les codes d'électricité nationaux et locaux.
6. Lorsqu'il n'y a pas de « dispositif de mise à la terre » dans la boîte murale, le NEC
2005, Article 404-9 autorise l'installation en remplacement d'une commande sans
liaison de terre à condition d'utiliser une plaque frontale en plastique non
combustible. Pour ce type d'installation, encapuchonner ou retirer le fil de terre vert
de la commande et utiliser une plaque frontale correspondante.
7. Pour les nouvelles installations, installer un interrupteur d'essai avant de faire la pose
de la commande.
8. Protégez la commande de la poussière et de la saleté lorsque vous peignez ou rebouchez.
9. Il est normal de sentir une chaleur au toucher de la commande intelligent lorsqu'il
fonctionne.
10. Nettoyer la commande avec un chiffon doux et humide seulement. Ne pas
utiliser de nettoyants chimiques.
Installation des commandes multiples
Lors de l'installation de plus d'une commande dans la même boîte murale, il peut être
nécessaire d'enlever toutes les sections latérales intérieures avant de faire le câblage
(voir ci-dessous). Avec des pinces, replier la section latérale de haut en bas jusqu'à ce
qu'elle se sépare. Répéter pour chacune des sections latérales à enlever. Remarque :
Les installations multiples ne requièrent aucun déclassement.
Les sections intérieures de
chaque commande sont
enlevées
Ce produit peut être protégé en vertu de l'un ou de plusieurs des brevets américains suivants : 4,835,343; 4,835,816;
5,191,971; et des brevets étrangers correspondants. NEC est une marque de commerce de National Fire Protection
Association, Quincy, Massachusetts.
Installation
1 1
Coupure de l'alimentation électrique.
• Couper l'alimentation au disjoncteur (ou retirer le fusible).
2 2
Dépose de la plaque murale et de l'interrupteur.
• Enlever la plaque murale et les vis de montage de l'interrupteur.
• Retirer délicatement l'interrupteur du mur (ne pas enlever les fils).
Mise en garde :
S'assurer que
l'alimentation
électrique est
coupée avant de
commencer.
3 3
Vérifier l'utilisation.
• L'interrupteur doit avoir deux fils isolés raccordés à deux vis et un fil de
cuivre ou vert raccordé à une vis verte. Remarque : Ne pas raccorder à un
luminaire.
Mise à la terre (fil de
cuivre dénudé ou fil vert)
037-106
Hubbell Incorporated (Delaware)
185 Plains Road
Milford, CT 06461-2420
(203) 882-4800
Français
®
Ne pas retirer
les sections
extérieures
Les deux sections latérales
de la commande mitoyen
sont enlevées
Continué au verso...
Fabriqué et imprimé aux É.-U.
8/06 N/P 037-106 Rev. A

Publicidad

loading

Resumen de contenidos para Hubbell homeSELECT RFSQ2F

  • Página 1 037-106 Continué au verso... or Green Wire) Made and printed in the U.S.A. Fabriqué et imprimé aux É.-U. Hubbell Incorporated (Delaware) Hubbell Incorporated (Delaware) 185 Plains Road 8/06 P/N 037-106 Rev. A 185 Plains Road 8/06 N/P 037-106 Rev. A...
  • Página 2 S.A. DE C.V. Tierra (cable de cobre defectos en materiales y mano de obra por un año a partir de su compra. Hubbell reparará o reemplazará el artículo a su juicio en un Av. Coyoacán # 1051 desnudo o verde) plazo de 60 días.

Este manual también es adecuado para:

Homeselect rsfsqf