Standby battery
Battery type
2 x12 Vdc Valve Regulated Lead Acid
Battery capacity
See below under Mechanical specifications.
Local Indicators
Mains LED (Green)
Mains present
Fault LED (Yellow)
Fault present: Output fuse fail or battery fuse
fail (requires load and battery to be
connected), loss of mains, output short
circuit or low output voltage.
See Diagnostic Table.
Charge LED (Orange)
Battery Charging

Diagnostic Table

M
F
C
AINS
AULT
HARGE
LED
LED
LED
(
)
(
)
(
GREEN
YELLOW
ORANGE
ON
OFF
OFF
ON
OFF
ON
1s ON,
ON
ON
1s OFF
or OFF
0.1s ON,
OFF
OFF
3s OFF
OFF
OFF
OFF
Signaling Outputs
Tamper
3 A, 125 Vdc N/C volt-free contacts.
Contact closed when the lid is closed and
unit securely mounted (TAMPER INACTIVE
condition).
0.1 A @ 60 Vdc N/O volt-free contacts.
GEN Fault (general)
Open when battery disconnected, output
fuse fail, battery fuse fail, and output short
circuit or low output voltage.
0.1 A @ 60 Vdc N/O volt-free contacts.
EPS Fault (mains)
Open when loss of mains for more than 8s.
Mechanical
Model
PM861, PM862
Enclosure dimensions
330 x 275 x 80
w x h x d (mm) [external]
2 x BS127N
Battery capacity
(7.2 Ah)
Weight (kg) excluding
2.98
battery
Environmental
Temperature
−10 to +40°C (operating) 95% RH non-condensing
−20 to +80°C (storage)
Connections
+O/P
+ve voltage O/P to load equipment
-O/P
−ve voltage O/P to load equipment
+BATT
Red lead to standby battery 1 positive
-BATT
Black lead to standby battery 2 negative
GEN Fault
Volt-free contacts for general faults
EPS Fault
Volt-free contacts for loss of mains indication
Specifications subject to change without notice.
PAK200535 • ISS 01A • 15APR13
S
TATUS
)
NORMAL - battery fully charged
NORMAL - battery charging
FAULT - see Signaling Outputs
FAULT - Mains Loss
PSU operating on battery standby
FAULT - No Output
Mains and Battery loss
PM863, PM865
330 x 275 x 80
2 x BS127N
(7.2 Ah)
3.30

Regulatory information

Manufactured for
UTC Fire & Security Americas Corporation, Inc.
1275 Red Fox Rd., Arden Hills, MN 55112-6943,
USA
EU authorized manufacturing representative:
UTC Fire & Security B.V., Kelvinstraat 7,
6003 DH Weert, The Netherlands
Year of
The last two digits of the date of manufacture
manufacture
(located on the product rating label) are the year
of manufacture.
Certification
European Union
2006/95/EC (Low Voltage directive): Hereby,
directives
UTC Fire & Security declares that this device is in
compliance with the essential requirements and
other relevant provisions of Directive 2006/95/EC.
2004/108/EC (EMC directive): Hereby, UTC Fire
& Security declares that this device is in
compliance with the essential requirements and
other relevant provisions of Directive
2004/108/EC
2002/95/EC (RoHs directive): Hereby, UTC Fire
& Security declares that this device is in
compliance with the essential requirements and
other relevant provisions of Directive 2002/95/EC
2002/96/EC (WEEE directive): Products marked
with this symbol cannot be disposed of as
unsorted municipal waste in the European Union.
For proper recycling, return this product to your
local supplier upon the purchase of equivalent
new equipment, or dispose of it at designated
collection points. For more information see:
www.recyclethis.info.
2006/66/EC (battery directive): This product may
contain a battery that cannot be disposed of as
unsorted municipal waste in the European Union.
See the product documentation for specific
battery information. The battery is marked with
this symbol, which may include lettering to
indicate cadmium (Cd), lead (Pb), or mercury
(Hg). For proper recycling, return the battery to
your supplier or to a designated collection point.
For more information see: www.recyclethis.info.

Contact information

For contact information visit our Web site:
www.utcfireandsecurity.com
3 / 16