Address Setting When Using Central Controller
Point description
Indoor unit 64
ON/ OFF state
Indoor unit 64
mode
Indoor unit 64
set temperature
Indoor unit
64 current fan
speed
Indoor unit 64
current tempera-
ture
Indoor unit 64
error code
Protocol
Extra
address
address
40665
40666
40667
40668
40669
40670
Point
type
AI
Integer between - 20 and
(Read)
16
State
1:ON,0:OFF
0:Auto,1:Fan 2: Cool-
4:Heating
ing,3:Dry,
1 to 16 represents
16
C to 30
C
0
0
0:Auto,1:Low 2:
Medium,3:High
50
Integer from 0 to 150