DuroZone
INSTALLATION INSTRUCTIONS
Model WRCD Remote Control Damper
4. Setting the Damper Zone/Address Using the Remote Control
Selection key
enter key
Selecting the Zone Number
A zone is a single WRCD damper or a group of WRCD dampers that are programmed to operate
together. Press and release the SEL key and the LCD will show the Zone Number. Use the Up and
Down keys to change the zone number and press the ENT key. The new Zone number and airflow
will be displayed. Zones are numbered 1 to 32.
Selecting the Address Number
The address is a convenient way to organize the zones (WRCD dampers). For example, an address
might be used to differentiate zones on one floor from zones on another floor or zones at the south
end of a building from zones at the north end.
Select a unique address (1 to 32). Press and release the SEL key twice and the LCD will show the
Address Number. Use the Up and Down keys to change the Address and press the ENT key.
Setting the Damper Zone and Address
To initiate the motor programming cycle press the small push button on the WRCD motor. The red
and green LEDs will blink. During the next 30 seconds the Zone and Address can be programmed
into the WRCD damper motor.
Press and release the SEL key three times and the LCD will show PRG DPR in the lower left corner.
Press the ENT key to program the Zone and Address in the WRCD damper.
Adjusting Airflow
After selecting the Zone number, press the Up and Down keys to set the airflow. Pressing the ENT
key sends the new airflow setting to the actuator. The percent airflow display is based upon the
range from the minimum flow position (displayed as 0%) to 100%
Push this button to enable
programming a new Zone
and Address number
Install all devices in accordance with applicable electrical and mechanical codes.
Duro Dyne East • Bay Shore, NY 11706 • Phone: 631-249-9000 • Fax: 631-249-8346
Duro Dyne Midwest • Fairfield, OH 45011 • Phone: 513-870-6000 • Fax: 513-870-6005
Duro Dyne West • Santa Fe Springs, CA 90670 • Phone: 562-926-1774 • Fax: 562-926-5778
Duro Dyne Canada • Lachine • Quebec • Canada • Phone: 514-422-9760 • Fax: 514-636-0328
©2009 Duro Dyne Corporation
Printed in USA 8/2009
BI035419
®
IMPORTANT
*Do not use other remote controls while programming is in progress.
*When batteries require replacement or are removed, the hand held remote
Up key
control will need to have the zone and address for each WRCD damper re-
entered. To eliminate the need to access the motor for re-programming,
during initial setup be sure to record the zone and address information and
Down key
keep it in an accessible location.
Low Battery Warning
When the batteries are low the display will show "Lob" and
the batteries should be changed. For longer life, use Lithium
AAA batteries.
MODEL
WRCD
www.durodyne.com
Email: durodyne@durodyne.com
:
ALL DUROZONe DAMPeRS FeATURe:
• 5 year limited warranty • Controlled bypass •
Maintenance free operation • Quick install mounting
clips (except Round Dampers) •100% factory testing •
Screwless terminals • Custom dampers and special
controls are available on request.
2
Red LED indicates damper
is in the minimum flow
position.
Green LED indicates
damper is in the maximum
flow position.