Output charts water AR200
AR200 W
Type
Fan
Airflow
position
[m
3
/h]
max
1000
AR210W
min
700
AR215W
max
1600
min
1000
AR220W
max
2000
min
1400
Type
Fan
Airflow
position
[m
/h]
3
AR210W
max
1000
min
700
AR215W
max
1600
min
1000
AR220W
max
2000
min
1400
Type
Fan
Airflow
position
[m
/h]
3
AR210W
max
1000
min
700
AR215W
max
1600
min
1000
max
2000
AR220W
min
1400
Type
Fan
Airflow
position
[m
/h]
3
AR210W
max
1000
min
700
AR215W
max
1600
min
1000
AR220W
max
2000
min
1400
*
) Recommended outlet air temperature for good comfort and optimized output.
1
*
) Nominal output at given supply and return water temperature.
2
See www.frico.se for additional calculations.
All manuals and user guides at all-guides.com
AR200
Supply water temperature:110 °C
Room temperature: +18 °C
Outlet air temperature: +35 °C*
Output
Return water
Water
temp.
flow
[kW]
[°C]
[l/s]
5,8
44,1
0,02
4,0
38,7
0,01
9,2
45,8
0,04
5,8
39,6
0,02
11,5
44,3
0,04
8,1
39,0
0,03
Supply water temperature:90 °C
Room temperature: +18 °C
Outlet air temperature: +35 °C*
Output
Return water
Water
temp.
flow
[kW]
[°C]
[l/s]
5,8
49,4
0,03
4,0
43,1
0,02
9,2
50,5
0,06
5,8
43,1
0,03
11,5
49,7
0,07
8,1
43,4
0,04
Supply water temperature: 80 °C
Room temperature: +18 °C
Outlet air temperature: +35 °C*
Output
Return water
Water
temp.
flow
[kW]
[°C]
[l/s]
5,8
52,6
0,05
4,0
45,8
0,03
9,2
53,3
0,08
5,8
45,3
0,04
11,5
52,9
0,10
8,1
46,1
0,06
Supply water temperature: 70 °C
Room temperature: +18 °C
Outlet air temperature: +35 °C*
Output
Return water
Water
temp.
flow
[kW]
[°C]
[l/s]
5,8
56,3
0,10
4,0
49,0
0,05
9,2
56,4
0,17
5,8
47,8
0,06
11,5
56,5
0,21
8,1
49,4
0,10
Water temperature: 110/80 °C
Room temperature: +18 °C
1
Pressure
Output *
Outlet
2
drop
air temp.
[kPa]
[kW]
[°C]
1,6
9,8
46,9
0,7
7,9
51,3
0,9
15,6
46,8
0,3
11,7
52,5
1,4
19,5
46,7
0,7
15,7
51,0
Water temperature: 90/70 °C
Room temperature: +18 °C
1
Pressure
Output *
2
Outlet
drop
air temp.
[kPa]
[kW]
[°C]
3,7
8,0
41,5
1,6
6,4
45,0
2,1
12,7
41,4
0,7
9,5
46,1
3,4
15,8
41,3
1,4
12,7
44,8
Water temperature: 80/60 °C
Room temperature: +18 °C
1
Pressure
Output *
Outlet
2
drop
air temp.
[kPa]
[kW]
[°C]
7,6
6,6
37,3
2,7
5,3
40,2
4,2
10,4
37,2
1,2
7,0
41,0
7,0
13
37,2
2,5
10,4
40,0
Water temperature: 70/50 °C
Room temperature: +18 °C
1
Outlet
Pressure
Output *
2
drop
air temp.
[kPa]
[kW]
[°C]
26,5
5,1
33,1
6,5
4,1
35,4
14,3
8,1
32,9
2,6
6,1
35,9
24,9
10,2
33,0
6,2
8,2
35,2
Water
Pressure
flow
drop
[l/s]
[kPa]
0,08
15,6
0,06
10,5
0,13
8,3
0,10
5,0
0,16
14,2
0,13
9,6
Water
Pressure
flow
drop
[l/s]
[kPa]
0,10
23,0
0,08
15,5
0,16
12,3
0,12
7,3
0,19
20,3
0,16
14
Water
Pressure
flow
drop
[l/s]
[kPa]
0,08
16,5
0,06
11,1
0,13
8,7
0,10
5,2
0,16
15
0,13
10,1
Water
Pressure
flow
drop
[l/s]
[kPa]
0,06
10,9
0,05
7,4
0,10
5,7
0,07
3,4
0,12
9,9
0,10
6,7
15