Important information regarding the refrigerant used
This product contains fl uorinated greenhouse gases covered by the Kyoto Protocol.
Do not vent gases into the atmosphere.
Refrigerant type: R410A
GWP
(1)
value:
(1)
GWP = global warming potential
Please fi ll in with indelible ink,
n 1 the factory refrigerant charge of the product,
n 2 the additional refrigerant amount charged in the fi eld and
n 1 + 2 the total refrigerant charge
on the refrigerant charge label supplied with the product.
The fi lled out label must be adhered in the proximity of the product charging port (e.g. onto the inside of the service cover).
(2)
In case of multiple indoor systems, only 1 label must be adhered*, mentioning the total factory refrigerant charge of all
indoor units connected in the refrigerant system.
Periodical inspections for refrigerant leaks may be required depending on European or local legislation. Please contact your
local dealer for more information.
* on the outdoor unit
Special Precautions When Dealing With R410A Unit
R410A is a new HFC refrigerant which does not damage the ozone layer. The working pressure of this new refrigerant is 1.6
times higher than conventional refrigerant (R22), thus proper installation / servicing is essential.
• Never use refrigerant other than R410A in an air conditioner which designed to operate with R410A.
• In 5MSY models, PVE oil is used as lubricant for R410A compressor, which is different from the mineral oil used for R22
compressor.
• To prevent mischarging, the diameter of the service port on the fl are valve is different from that of R22.
• Use tools and materials exclusively for refrigerant R410A. Tools exclusively for R410A are manifold valve, charging hose,
pressure gauge, gas leak detector, fl are tools, torque wrench, vacuum pump and refrigerant cylinder.
• As an R410A air conditioner incurs higher pressure than R22 units, it is essential to choose the copper pipes correctly. Never
use copper pipes thinner than 0.8mm even though they are available in the market.
• If the refrigerant gas leakage occurs during installation / servicing, be sure to ventilate fully. If the refrigerant gas comes
into contact with fi re, a poisonous gas may occur.
• When installing or removing an air conditioner, do not allow air or moisture to remain in the refrigerant cycle.
1 IM 5MSY-1009(1)_EN.indd 03
1 IM 5MSY-1009(1)_EN.indd 03
All manuals and user guides at all-guides.com
1975
1 factory refrigerant charge of the product:
see unit name plate
2 additional refrigerant amount charged in the fi eld
3 total refrigerant charge
4 Contains fl uorinated greenhouse gases covered by the Kyoto Protocol
5 outdoor unit
6 refrigerant cylinder and manifold for charging