5b
1
2
31 Nm (274.37 lb-in)
6
XKSA
1
2
Z 2
1 Nm
(8.85 lb-in)
Use of Terminal Cover NZM3-XKSA on UL/CSA models:
– Mechanical (tunnel) lug connector kits ...XKA... come supplied with terminal cover NZM3-XKSA.
Top and bottom portions of the terminal cover are mounted as shown in above diagrams and installation is always required.
– Terminal cover NZM3-XKSA maintains electrical clearances and provides protection against accidental contact
with live parts in the incoming and outgoing supply circuit terminations of the Circuit-Breaker or switch
– NZM3-XKA2 Maximum allowed rated current: 550 A
Emergency On Call Service: Local representative (http://www.eaton.eu/aftersales) or +49 (0) 180 5 223822 (de, en)
Eaton Industries GmbH, Hein-Moeller-Straße 7-11, 53115 Bonn, Germany
© 2002 by Eaton Industries GmbH,
www.eaton.eu/documentation
8 mm
XKSA
2
1 x 50 - 240 mm
2
2 x 50 - 240 mm
1 x AWG 0 - 500 kcmil
2 x AWG 0 - 500 kcmil
Use ferrules with flexible and highly flexible conductors.
Bei feindrähtigen und hochflexiblen Leitern Aderendhülsen verwenden.
Pour les conducteurs souples et extra-souples, utiliser des embouts.
Para conductores flexibles y muy flexibles deben utilizarse terminales.
Per conduttori flessibili e altamente flessibili utilizzare capicorda.
对于多股和非常容易弯曲的线缆可以使用线缆衬套
Для тонкопроволочных и очень гибких жил требуется использовать наконечники.
All Rights Reserved
01/17 IL01210007Z 12256584/DE17
Printed in Germany (01/17)
3/3
Doku