6 STANDARDS

The AVR-A-OPT-06 voltage regulators comply with the following international standards:
Standard
IEC 61000-4-5 – Surge immunity test
IEC 61000-4-4 - Electrical fast transient/burst immunity
test
IEC 61000-4-3 – Radiated, radio-frequency,
electromagnetic field immunity test
IEC 61000-4-2 - Electrostatic discharge immunity test
IEC 61000-4-11 - Voltage dips, short interruptions and
voltage variations immunity tests
IEC 61000-4-6 - Immunity to conducted disturbances,
induced by radio-frequency fields

7 IDENTIFICATION TAG

Model:
Power Input
Excitation Voltage
Excitation Current
Sensing Voltage
The above example shows the main characteristics described in the nameplate/ID tag that needs to be checked before installation.
NOTE
The ID tag is affixed on the backside of the regulator, and to the Installation Guide.
1.
16 l Automatic Voltage Regulator – AVR-A-OPT-06 400Hz
Table 6.1: Standards
Asymmetrical: 4kV Symmetrical: 4kV
5Khz repetitions, +/- 2kV peak voltage
10V/m field for a frequency range from 80MHz to 1GHz. A
10% maximum variation is allowed at the output voltage for a
radiated frequency between 160MHz and 280MHz. For all
other frequencies the equipment doesn't present variations
Contact: 4kV load;
Through the air: 8kV load.
Dip f 30db to 95db dips
10V amplitude, 150kHz to 80Mhz
Figure 7.1: Identification tag
Level
Operating Frequency
Performance
Criteria
B
B
A
B
C and B
A