MINIMUM DEIONIZATION SPACE WITHOUT EARTHED METALLIC CONSTRUCTIONS
MINIMÁLNÍ DEIONIZA•NÍ PROSTOR BEZ KOVOVÝCH UZEMN NÝCH KONSTRUKCÍ
C=20
B=75
H=30
A
...
- minimum distance between the circuit breaker and bare wall (this is valid for insulated conductors, cables,
flexi bars or rear connection)
A...
- minimální vzdálenost mezi jisti!em a neizolovanou uzemn"nou st"nou (platí pro izolované vodi!e, kabely, flexibary nebo zadní p#ívod)
A1
..
-
minimum length of insulation of bare conductors (with use of insulating barriers from 50 mm to max. 100 mm, possibly with
additional insulation of conductors above the barriers to A1 level)
A1..
- minimální délka izolace holých vodi!$ (použitím izola!ních p#epážek od 50 mm do max. 100 mm, p#ípadn" dopl%kovou
izolací vodi!$ nad p#epážkami minimáln" na hodnotu A1)
A2
..
- minimum distance between the circuit breaker and bare wall (this is valid for bare conductors and busbars), ...
between the conductor and busbar, ... between two circuit breakers installed vertically above each other,
... between bare leads of two circuit breakers above each other
A2..
- minimální vzdálenost mezi jisti!em a neizolovanou uzemn"nou st"nou (platí pro neizolované vodi!e a sb"rnice), ... mezi jisti!em a sb"rnicí,
... mezi dv"mi jisti!i umíst"nými vertikáln" nad sebou, ... mezi neizolovanými p#ívody dvou jisti!$ nad sebou
C, D, E, F, G
...
- minimum distance between circuit breaker and bare earthed wall
C, D, E, F, G ... - minimální vzdálenost mezi jisti!em a neizolovanou uzemn"nou st"nou
H
..
- minimum distance between bare conductors
H.. - minimální vzdálenost mezi neizolovanými vodi!i
1)
U >
415 V a.c.
n
)
U
2
415 V a.c.
n
B=75
B=100
- 7 -
INSULATING BARRIERS
C=20
IZOLA•NÍ P EPÁŽKY
E=70
BC160...
F=0
1)
G=40
2)
G=0
991119i