Available Louvers: indica la posición de las lamas disponibles en la unidad.
16
This is Read only object.
External Temp: The Building management system can obtain the external
35
temperature. These are read only objects.
Return Temp: The Building management system can obtain the return
36
temperature. These are read only objects.
Liquid pipe Temperature: The Building management system can obtain the
37
exchange heat temperature of indoor unit. These are read only objects.
Gas Pipe Temp Indoor Unit: The Building management system can obtain
38
the gas pipe temperature of indoor unit. These are read only objects.
42
Position expansion valve Indoor Unit
Work Temperature: The Building management system can obtain the work
53
temperature for any zone. These are read only objects.
54
Speeds numeric
55
Error value
56
Modbus address
57
Config port baudrate
58
Config port parity
Heater status.
59
Monitor the Aux heater status (digital output contact).
60
Digital Input status. Monitor the digital input operation status
Notes:
(*) Maximum/Minimum limits depend on your A/C unit. (**) Should be greater than 0.
Bit 0: Auto U/D
Bit 3: Swing U/D
Bit 4: Swing L/R
Bit 5: Swril
0x03, 0x04
Bit 8-11: Vertical
positions (0-7)
Bit 12-15: Horiz.
Positions (0-7)
Temperature x 10
0x03, 0x04
Temperature x 10
0x03, 0x04
Temperature x 10
0x03, 0x04
Temperature x 10
0x03, 0x04
Pulse units
0x03, 0x04
Temperature x 10
0x03, 0x04
Example: 22.5 ºC
is 225
0x03, 0x04,
0,1,2,3....
0x06, 0x10,
0 : Auto
0x16
Value of error
0x03, 0x04
Example: 0x24
0x03, 0x04,
Modbus slave
0x06, 0x10,
address (Default 1)
0x16
0: 100 bps
1: 300 bps
2: 500 bps
3: 1200 bps
4: 2400 bps
0x03, 0x04,
5: 4800 bps
0x06, 0x10,
6: 7800 bps
0x16
7: 9600 bps
8: 19200 bps
(default)
9: 57600 bps
10: 115200 bps
0: None
0x03, 0x04,
1: Odd
0x06, 0x10,
0x16
2: Even (default)
0: Deactivated
0x03,0x04
1: Activated
0: Deactivated
0x03,0x04
1: Activated
· · · ·
·
·
· · · ·
·
·
·
·
·
·
· · · ·
· · · ·
· · · ·
· · · ·
· · · ·
· · · ·
· ·
· ·