Descargar Imprimir esta página

Temper CS-INV-S-METER Manual De Instrucciones página 15

Publicidad

Idiomas disponibles

Idiomas disponibles

CS-INV-S-METER
Environment
Operating temperature
Storage and transportation temperature
Reference temperature
Relative humidity
Altitude
Warm up time
Installation category
Mechanical Environment
Electromagnetic environment
Degree of pollution
Output
Pulse Output
The meter provides two pulse outputs. Both pulse outputs are passive type.
Pulse output 1 is configurable. The pulse output can be set to generate pulses to represent total / import/export
kWh or kVArh.
The pulse constant can be set to generate 1 pulse per: 0.001(default) /0.01/0.1/1kWh/kVArh.
Pulse width: 200/100/60ms
Pulse output 2 is non-configurable. It is fixed to import kWh. The constant is 1000imp/kWh.
RS485 output for Modbus RTU
The meter provides a RS485 port for remote communication. Modbus RTU is the protocol applied. For Modbus
RTU, the following RS485 communication parameters can be configured from the Set-up menu.
Baud rate: 1200, 2400, 4800, 9600 bps. Default: 2400bps
Parity: NONE/EVEN/ODD
Stop bits: 1 or 2
Modbus Address: 1 to 247
Mechanics
Din rail dimensions
Mounting
Ingress protection
Material
Bidirectional energy meter - Single-phase system s
-25℃ to +55℃
-40℃ to +70℃
23℃±2℃
0 to 95%, non-condensing
up to 2000m
5s
CAT II
M1
E2
2
36x100x63 (WxHxD) DIN 43880
DIN rail 35mm
IP51 (indoor)
self-extinguishing UL94V-0
- 15 -

Publicidad

loading

Este manual también es adecuado para:

0700329