4" CLAMP STYLE REMODEL RECESSED HOUSINGS
WARNING: For your safety, read and understand instructions completely before starting installation.
Before wiring to power supply, turn off electricity at the fuse or circuit breaker box.
NOTE: Juno recessed fixtures are designed to meet the latest code requirements and are listed in compliance with UL/cUL 1598.
Before attempting installation of any recessed lighting fixture, check your local electrical building code. This code sets the wiring
and installation requirements for your locality and should be understood before starting your work. Use of Non-Juno trims voids
Juno warranty.
SAVE THESE INSTRUCTIONS
TYPE TC FOR
NON-INSULATED CEILINGS
Figure 1
Juno Type TC fixtures are designed for install-
ations where housing and J-Box will not come
into contact with insulation. Blinking light after
installation indicates that improper bulb or trim
is being used or that fixture has been improperly
covered with insulation.
* In U.S., insulation must be spaced 3" away from
the housing and J-Box.
INSTALLATION STEPS
Figure 2
Step 1. Locate center of proposed opening on
ceiling and use template to mark and accurately
cut a 4-3/8" opening. (Fig. 2)
Step 2. Follow steps 1-4 under electrical
connection.
Step 3. Position spring clamps inside housing
as shown prior to insertion into ceiling, then
insert housing through ceiling opening (Fig. 3).
Position flange flush to ceiling (Fig. 4).
Slide spring clamp ends through housing slots;
tighten screws to clamp fixture to ceiling using
#2 Phillips or #2 Square driver (Fig. 4).
(Note: To remove housing from ceiling, loosen
screws until spring clamps can return to internal
cavity of housing.)
Step 4. Install trim using push-in springs
pro-vided (Fig. 5). Remove socket paint protec-
tor cover and install proper lamp (light bulb) as
listed on housing label.
1300 South Wolf Road • Des Plaines, IL 60018 • Phone 800-323-5068 • Visit us at www.junolightinggroup.com
INSTALLATION INSTRUCTIONS
Housing Slot
Spring Clamp
Figure 3
Housing Slot
Spring Clamp
Figure 4
Figure 5
Figure 6
© 2016 Acuity Brands Lighting, Inc.
ELECTRICAL CONNECTION
INSTRUCTIONS
120V
Figure 7
Step 1. Provide electrical service according to
your local electrical code to the wiring box locat-
ed on the remodel housing. Supply wire insula-
Housing Slot
tion must be rated for at least 90°C.
Step 2. Remove wiring box cover. Remove the
Spring Clamp
appropriate knock-out to connect flexible metal
conduit or non-metallic cable to wiring box with
proper connectors (by others) (Fig. 6).
Tighten
screws
Step 3. Connect supply wires to fixture wires
utilizing the push-in connectors provided, so as
to cover all bare current-carrying conductors.
Connect black fixture wire to hot, white fixture
wire to neutral and green fixture wire to ground
(Fig. 7).
Step 4. Place all wiring and connections back in
wiring box and replace cover.
Printed in U.S.A.
Fixture Junction Box
Green
Thermal Protector
Black
White
Lamp Socket
Rev 2/15
pg 1 of 1
P3772