Multiple fan coil unit installation
GLOBE
VALVE
** All three fan coil units to serve one area with a common
thermostat. When temperature has reached set point,
thermostat will send signal to 3-way valve to divert
water away.
GUIDELINES FOR VALVE AND FITTING INSTALLATION
a. Gate valves (shut-off) are installed in the entering and leaving
piping to the chiller and fan coil unit. This is to permit servicing
and replacement of the equipment without draining the
system. A globe valve may be used to serve as one of the
shut-off valve and in addition to balance the rate.
b. Valves and fittings using threaded or welded joints will require
unions to permit easy removal for servicing or replacement.
Unions are usually located between each gate valve and
the equipment. Unions are also place before and after the
control valve, and in the branch of the 3-way valve.
If flange joints are used, the need for unions is eliminated.
Schematic Diagram For Mini Air Cooled Chiller Installation
MAIN SUPPLY
CHECK VALVE
FLEXIBLE JOINT
GLOVE VALVE
MINI AIR
COOLED CHILLER
All manuals and user guides at all-guides.com
FCU 1
FCU 2
c. Locate the control valve in between the gate valve and the
d. Strainers, thermometers and pressure gauges are located
OVER FLOW PIPE TO NEAREST DRAIN / FLOOR TRAP
MAKE-UP
WATER TANK
PRESSURE GAUGE
THERMOMETER
BALL VALVE
P
T
GATE VALVE
STRAINER
P
T
1-4
AIR VENT
FCU 3
T
T
3-WAY
DIVERTING
VALVE
equipment to permit removal of the control valve without
draining the system.
between the gate valve and the equipment.
The following diagrams illustrate examples of piping layout:
MOTORIZED 3 WAY VALVE
BALL VALVE
WITH THERMOSTAT
AIR VENT
GATE VALVE
STRAINER
T
M
FLEXIBLE HOSE
DRAIN PIPE TO NEAREST DRAIN / FLOOR TRAP
T
M
M
T
M
T
T
M
DUCTING
RC SLAB
FCU 1
CEILING
RC SLAB
FCU 2
CEILING
RC SLAB
FCU 3
CEILING
RC SLAB
FCU 4
CEILING
RC SLAB
FCU 5
CEILING