6. Commissioning, operation
6.2 Electrical mounting
Only use original accessories. For accessories see data sheet PE 81.61.
WARNING!
The instrument shield does not act as a protective conductor for protection of personnel, rather as a
functional ground in order to shield the instrument from electromagnetic fields.
6.2.1 Connection assembly
For instruments with ratiometric output signals, a shielded cable must be used. The cable shield must be grounded,
if the cable is longer than 30 m or leaves the building.
Use a cable with suitable characteristics for the particular operating conditions.
For cable variants, strain relief must be employed.
Cable with ventilation tubes must be vented to atmosphere.
The instrument must be earthed via the process connection!
Select a cable diameter that matches the cable gland of the plug. Make sure that the cable gland of the mounted
plug has a tight fit and that the seals are present and undamaged. Tighten the threaded connection and check that
the seal is correctly seated, in order to ensure a tight seal.
For cable outlets, make sure that no moisture enters at the cable end.
Pin assignment see test report.
6.2.2 Setting up a voltage supply
The voltage supply is made via a power supply unit or a control unit which provides the energy limitation.
The power supply for the pressure transmitter must be made via an energy-limited electrical circuit in accordance with
section 9.4 of UL/EN/IEC 61010-1, or an LPS to UL/EN/IEC 60950-1, or class 2 in accordance with UL1310/UL1585
(NEC or CEC). The power supply must be suitable for operation above 2,000 m should the pressure transmitter be
used at this altitude.
WIKA operating instructions pressure transmitter, model S-20
EN
19