8. Test run
• On wired remote controller
Check code displayed in the LCD.
• If the unit cannot be operated properly after the above test run has been performed, refer to the following table to remove the cause.
Symptom
Wired remote controller/ RF thermostat
PLEASE WAIT
PLEASE WAIT → Error code
Display messages do not appear even
when operation switch is turned ON
Note:
Operation is not possible for about 30 seconds after cancellation of function selection. (Correct operation)
For description of each LED (LED1, 2, 3) provided on the indoor controller, refer to the following table.
LED1 (power for microcomputer)
LED2 (power for wired remote controller)
LED3 (communication between indoor and outdoor units)
Fig. 8-1
For about 2 minutes
• For about 2 minutes following power-on, operation of the remote controller is not
following power-on
possible due to system start-up. (Correct operation)
• Connector for the outdoor unit's protection device is not connected.
After about 2 minutes
• Reverse or open phase wiring for the outdoor unit's power terminal block
has expired following
• Incorrect wiring between indoor and outdoor units (incorrect polarity of S1, S2, S3)
power-on
• Remote controller wire short
Indicates whether control power is supplied. Make sure that this LED is always lit.
Indicates whether power is supplied to the wired remote controller.
Indicates state of communication between the indoor and outdoor units. Make sure that this LED
is always blinking.
Cause
8.4. Check drainage
(Fig. 8-1)
• During the test run, ensure the water is being properly drained out and that no
water is leaking from joints.
• Always check this during installation even if the unit is not required to provide
cooling/drying at that time.
• Similarly, check the drainage before finishing ceiling installation in a new premis-
es.
(1) Remove the cover of the water supply inlet and add about 1000 cc, 1/4 gal of
water using a water supply pump etc. During this process, be careful not to
spray water into the drain pump mechanism.
(2) Confirm that water is being drained out through the drainage outlet, after switch-
ing over from remote control mode to test run mode (cooling mode).
(3) After checking the drainage, ensure that the cover is replaced and the power
supply is isolated.
(4) After confirming the drainage system is functioning, replace the drain plug.
Insert the pump end 3 to 5 cm, 1-3/16 to 2 inch
Cover of water supply inlet
About 1000 cc, 1/4 gal
Water
Drain plug
13