3. Installation Of LCD Remote Controller
3.1 Accessories
The following accessories are included together with this manual. If any part is
missing, contact your dealer immediately.
1
Remote controller
2
Wooden screw 4.1 x 16 (2 pieces) & machine screw (2 pieces)
3
Instruction manual
4
Battery
3.2 Step-by-step Guide
i)
First, open up the casing of the LCD remote controller into its top and bottom
case using a screwdriver. To do this, insert the screwdriver into the lower slot and
slide it in the outward direction.
ii)
Fix the bottom case onto the wall with the 2 wooden screws provided. Then,
insert the 4 connecting wires (from the main board) through the slot on the lower
center of the case as shown below.
iii) Connect one end in each of the 3 wires to the terminal block behind the top case
as illustrated.
iv) To select cooling only model or heatpump model, some adjustment required in
the dip switch setting.
v)
Fasten back the top and bottom case into place. Hook the two upper claws into
their respective slots and snap the lower part shut.
Lower slot
for opening LCD
casing
Yellow wire
Tx/RCV
Black wire
GND
Red wire
+5V
White wire
Tx
Connection behind
top case
Dip switch setting for model selection
Pin
Function
JH&JD
COOL, DRY, FAN
COOL, DRY, FAN, HEAT
RTC
No real time clock
Real time clock
NO DRY
Without Dry function
Dry function
OM-NET2-1102-Acson
LCD Remote
(Top case)
2 x Wooden
screw
LCD Remote
(Bottom case)
Remarks
JH - OFF, JD - ON
JH - ON, JD - OFF
RTC - OFF
RTC - ON
NO DRY - ON
NO DRY - OFF
3
3
Connection at
main board
Connection
wires
Model
Cooling only
Heatpump
11/21/05, 10:59 AM