9.2. Connecting remote controller, indoor
and outdoor transmission cables
(Remote contoroller is optionally available.)
Connect indoor unit TB5 and outdoor unit TB3. (Non-polarized 2-wire)
The "S" on indoor unit TB5 is a shielding wire connection. For specifications
about the connecting cables, refer to the outdoor unit installation manual.
Install a remote controller following the manual supplied with the remote con-
troller.
Connect the "1" and "2" on indoor unit TB15 to a MA remote controller. (Non-
polarized 2-wire)
Connect the "M1" and "M2" on indoor unit TB5 to a M-NET remote controller.
(Non-polarized 2-wire)
Connect the remote controller's transmission cable within 10 m using a 0.75 mm
core cable. If the distance is more than 10 m, use a 1.25 mm
[Fig. 9.2.1] (P.4) MA Remote controller
[Fig. 9.2.2] (P.4) M-NET Remote controller
A Terminal block for indoor transmission cable
B Terminal block for outdoor transmission cable
C Remote controller
DC 9 to 13 V between 1 and 2 (MA remote controller)
DC 24 to 30 V between M1 and M2 (M-NET remote controller)
[Fig. 9.2.3] (P.4) MA Remote controller
[Fig. 9.2.4] (P.4) M-NET Remote controller
A Non-polarized
C Remote Controller
The MA remote controller and the M-NET remote controller cannot be used at
the same time or interchangeably.
Note:
Ensure that the wiring is not pinched when fitting the terminal box cover.
Pinching the wiring may cut it.
Caution:
Install wiring so that it is not tight and under tension. Wiring under tension
may break, or overheat and burn.
Fix power source wiring to control box by using buffer bushing for tensile force.
(PG connection or the like.) Connect transmission wiring to transmission ter-
minal block through the knockout hole of control box using ordinary bushing.
After wiring is complete, make sure again that there is no slack on the connec-
tions, and attach the cover onto the control box in the reverse order removal.
Caution:
Wire the power supply so that no tension is imparted. Otherwise disconnec-
tion, heating or fire result.

9.3. Connecting electrical connections

Verify that the model name on the operating instructions on the cover of the control
box is the same as the model name on the nameplate.
Step 1
Remove the screws holding the terminal box cover in place. (2 screws)
[Fig. 9.3.1] (P. 4)
A Screws
Note:
Ensure that the wiring is not pinched when fitting the terminal box cover.
Pinching the wiring may cut it.
Caution:
Install wiring so that it is not tight and under tension. Wiring under tension
may break, or overheat and burn.
Fix power source wiring to control box by using buffer bushing for tensile force.
(PG connection or the like.) Connect transmission wiring to transmission ter-
minal block through the knockout hole of control box using ordinary bushing.
After wiring is complete, make sure again that there is no slack on the connec-
tions, and attach the cover onto the control box in the reverse order removal.
[Fig. 9.3.2] (P. 4)
A To prevent external tensile force from applying to the wiring connection section of
power source terminal block use buffer bushing like PG connection or the like.
B Power source wiring
D Use ordinary bushing
Caution:
Wire the power supply so that no tension is imparted. Otherwise disconnec-
tion, heating or fire result.
10
2
2
junction cable.
B Upper level (TB15)
D Lower level (TB5)
B Terminal box cover
C Tensile force
E Transmission wiring

9.4. Selecting the static pressure

The external static pressure can be changed over as required. For the selection of
the static pressure, insert an attachment between the connector of the motor lead
wire and the control box.
The relationship between the attachment, voltage and the external static pressure
is shown below.
Model
Attachment
208 V
Red
50
White
Blue
80
170
Red
60
85
White
35
Blue
Red
50
White
Blue
140
170
Red
60
White
85
Blue
35

9.5. Setting addresses

(Be sure to operate with the main power turned OFF.)
[Fig. 9.5.1] (P. 4)
<Address board>
There are two types of rotary switch setting available: setting addresses 1 to
9 and over 10, and setting branch numbers.
1 How to set addresses
Example: If Address is "3", remain SW12 (for 1 to 9) at "0", and match
SW11 (for over 10) with "3".
2 How to set branch numbers (Series R2 only)
Match the indoor unit's refrigerant pipe with the BC controller's end con-
nection number. Remain other than R2 at "0".
The rotary switches are all set to "0" when shipped from the factory. These
switches can be used to set unit addresses and branch numbers at will.
The determination of indoor unit addresses varies with the system at site. Set
them referring to technical data.
Notes:
Please set the switch SW5 according to the power supply voltage.
Set SW5 to 240 V side when the power supply is 230 and 240 volts.
When the power supply is 220 volts, set SW5 to 220 V side.

9.6. Forced Heating

When THERMO is set to OFF, ventilation is selected and external air is drawn
into the room without being processed in any way.
When intake temperature (outdoor temperature) is 5° CDB or less, forced heat-
ing may be used to prevent any discomfort due to the cold air. Set DIP switch
SW1-7 on the address board to ON to select forced heating. The fan will stop if a
problem occurs while SW1-7 is set to ON.
220 V
230 V
240 V
190
210
220
115
130
170
40
50
80
190
220
115
130
40
50
190
220
240
115
130
170
50
60
100
190
220
115
130
50
60