Indoor Unit Fixing; Drainage; Outdoor Unit; Installation Place - Toshiba 137SKV Serie Manual Del Usuario

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 11
NOTE
If the pipe is bent incorrectly, the indoor unit may unstably be set on the wall.
After passing the connecting pipe through the pipe hole, connect the
connecting pipes to the auxiliary pipes and wrap the facing tape around
them.
CAUTION
• Bind the auxiliary pipes (two) and connecting cable with facing tape
tightly. In case of leftward piping and rear-leftward piping, bind the
auxiliary pipes (two) only with facing tape.
Auxiliary pipes
Installation plate
• Carefully arrange pipes so that any pipe does not stick out of the rear
plate of the indoor unit.
• Carefully connect the auxiliary pipes and connecting pipes to one
another and cut off the insulating tape wound on the connecting pipe to
avoid double-taping at the joint; moreover, seal the joint with the vinyl
tape, etc.
• Since dewing results in a machine trouble, make sure to insulate both
connecting pipes. (Use polyethylene foam as insulating material.)
• When bending a pipe, carefully do it, not to crush it.

Indoor Unit Fixing

1. Pass the pipe through the hole in the wall and hook the indoor unit on the
installation plate at the upper hook.
2. Swing the indoor unit to right and left to confi rm that it is fi rmly hooked up on
the installation plate.
3. While pressing the indoor unit onto the wall, hook it at the lower part on the
installation plate. Pull the indoor unit toward you to confi rm that it is fi rmly
hooked up on the installation plate.
Hook here.
1
1
Installation plate
2
Hook
• For detaching the indoor unit from the
installation plate, pull the indoor unit toward
you while pushing its bottom up at the
specifi ed parts.

Installation Place

• A place which provides the spaces around the outdoor unit as shown in the
diagram
• A place which can bear the weight of the outdoor unit and does not allow an
increase in noise level and vibration
• A place where the operation noise and discharged air do not disturb your
neighbors
• A place which is not exposed to a strong wind
• A place free of a leakage of combustible gases
• A place which does not block a passage
• When the outdoor unit is to be installed in an elevated position, be sure to
secure its feet.
• The allowable pipe length is up to 10 m for RAS-107SAV and 20 m for RAS-
137SAV. If the length is over 15 m, add 20 g of refrigerant for every additional
meter of the pipe length.
• The allowable height of outdoor-unit installation site is up to 8 m for RAS-
107SAV and 10 m for RAS-137SAV.
• A place where the drain water does not raise any problems
1110251210-EN.indd 5
1110251210-EN.indd 5
Indoor unit
Connecting cable
Press
(unhook)
Push
Push

OUTDOOR UNIT

OUTDOOR UNIT
5

Drainage

1. Run the drain hose sloped downwards.
NOTE
• The hole should be made at a slight downward slant on the outdoor side.
Do not rise the
drain hose.
50 mm
or more
Do not put the
drain hose end
into water.
2. Put water in the drain pan and make sure that the water is drained out of
doors.
3. When connecting extension drain hose, insulate the connecting part of
extension drain hose with shield pipe.
Shield pipe
Drain hose
Inside the room
CAUTION
Arrange the drain pipe for proper drainage from the unit.
Improper drainage can result in dew-dropping.
This air conditioner has the structure designed
to drain water collected from dew, which forms
on the back of the indoor unit, to the drain pan.
Therefore, do not store the power cord and other
parts at a height above the drain guide.
CAUTION
1. Install the outdoor unit without anything blocking the air discharging.
2. When the outdoor unit is installed in a place always exposed to strong
wind like a coast or on a high storey of a building, secure the normal fan
operation using a duct or a windshield.
3. In particularly windy areas, install the unit such as to avoid admission of
wind.
4. Installation in the following places may result in trouble.
Do not install the unit in such places.
• A place full of machine oil
• A saline-place such as the coast
• A place full of sulfi de gas
• A place where high-frequency
waves are likely to be generated
as from audio equipment, welders,
and medical equipment
Do not form the
drain hose into
a wavy shape.
Do not put the
drain hose end
in the drainage ditch.
Extension drain hose
Wall
Drain
guide
Space for pipes
Strong
wind
11/12/09 3:03:08 PM
11/12/09 3:03:08 PM

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

137sav serieRas-107

Tabla de contenido