F
+ 3.0
Imax
F
+ 4.0
Omax
F
- 3.0
Imin
F
- 4.0
Omin
F
adjustable
Imin
F
adjustable
Imax
F
adjustable
Omin
F
adjustable
Omax
Reconnection
Reconnection Time
Reconnection Time adjustable
F
reconnect value
max
F
reconnect value
min
U
reconnect value
min
U
reconnect value
max
F
reconnect value adjustable
min
F
reconnect value adjustable
max
U
reconnect value adjustable
min
U
reconnect value adjustable
max
U
AC Voltage
AC
[s]
Unit: Seconds
[cyl]
Unit: Cycles (1)
U
U Inner Limit min (min. inner limit voltage)
Imin
U
U Inner Limit max (max. inner limit voltage)
Imax
U
U Outer Limit min (min. outer limit voltage)
Omin
U
U Outer Limit max (max. outer limit voltage)
Omax
U
nominal Voltage
nom
F
F Inner Limit min (min. inner limit frequency)
Imin
F
F Inner Limit max (max. inner limit frequency)
Imax
F
F Outer Limit min (min. outer limit frequency)
Omin
F
F Outer Limit max (max. outer limit frequency)
Omax
Frequency (for Setup HI1)
F [Hz]
Clearing Time [s]
Clearing Time [cyl]
> 63.0
1258
> 64.0
< 57.0
1258
< 56.0
50.00 -
0.016 - 600
65.00
1 - 36000
50.00 -
0.016 - 600
65.00
1 - 36000
50.00 -
0.016 - 600
65.00
1 - 36000
50.00 -
0.016 - 600
65.00
1 - 36000
for 60 Hz setups
300 s
5 - 900 s
< 60.5 Hz / < 60.1 Hz ***
> 59.3 Hz / > 59.9 HZ ***
U > 88 %
U < 106 % / U < 110 % ***
50.0 - 65.0 Hz
50.0 - 65.0 Hz
U > 50 % - U > 95 %
U < 101% - U < 120%
***
Setup HI1
Accuracy
21.0
Voltage trip limit accuracy
+/- 1.0 % of Unom
0.16
Frequency trip limit accuracy
9
+/- 0.05 Hz
21.0
Trip time accuracy
+/- 16.7 ms * (1 cycle)
+/- 20.0 ms ** (1 cycle)
0.16
Detection time
9
25 ms * (1.5 cycles)
30 ms ** (1.5 cycles)
*
**
default set values:
U < 50%, 50 ≤ U < 88 %, 110 < U < 120 %,
U ≥ 120 %, F
F
- 0.7, F
Imin
reconnection time
The field adjustable trip points can be set at
the PROFI Service Menu. The access code
will be provided by Fronius upon request.
60 Hz
50 Hz
for 50 Hz setups
300 s
5 - 900 s
< 50.5 Hz
> 48.0 Hz
U > 88 %
U < 106 %
45.0 - 55.0 Hz
45.0 - 55.0 Hz
U > 50 % - U > 95 %
U < 101% - U < 120%
+0.5, F
+ 2.0,
Imax
Omax
- 3.0,
Omin
53