Installation
Step 3: Connect Equipment to PDU. Connect equipment
to the PDU with user-supplied IEC-320 interconnection
cords. Be careful not to exceed the load rating for each
outlet nor the total load rating for the PDU. Note:
Interconnection cords (IEC-320-C13 to IEC-320-C14) are
available from Tripp Lite. Call 773-869-1234 (Part #
P004-006).
Step 4: Optional Installation (Not Shown). The input
power cord's IEC-320-C20 connector and the IEC-
320-C14 adapter can each connect to user-supplied
power cords with plugs appropriate for the installation
site's utility outlets. This capability is useful for connecting
the PDU to various international outlet types.
Features
A
A
IEC-320-C19 Outlets
B
IEC-320-C13 Outlets
C
Circuit Breaker: If the current drawn by the equipment connected to the PDU exceeds the
Maximum Load Rating for longer than a few seconds, the circuit breaker will activate and
interrupt AC power to prevent possible damage. When the circuit breaker activates, its plunger
will pop up. Disconnect excess equipment from the PDU and allow the breaker to cool one
minute before depressing the plunger to reset the breaker.
D
NEMA 5-15P connects to NEMA 5-15R outlet.
E
NEMA 5-20P connects to NEMA 5-20R outlet.
F
NEMA L5-20P connects to NEMA L5-20R outlet.
G
NEMA L6-20P connects to NEMA L6-20R outlet.
H
IEC-320-C14 connects to user-supplied power cord with IEC-320-C13 or to a UPS/power
supply.
I
IEC-320-C20 connects to user-supplied power cord with IEC-320-C19, to an input adapter or
to a UPS/power supply.