System Wiring - System Sensor 9400XE FAAST Manual De Instrucciones

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

FIGURE 3. POWER AND ALARM CONNECTION BLOCK
TABLE 1. TERMINAL DESIGNATIONS
TERMINAL
BLOCK
T1
External Power – Powers Aspirating Smoke Detector
T2
Not used
T3
RS 485 Rx
Rx and Tx can be wired in a half duplex configuration
T4
RS 485 Tx
Rx and Tx can be wired in a half duplex configuration
T5
Alert Relay – Maintains state on loss of power
T6
Action1 Relay – Maintains state on loss of power
T7
Action2 Relay – Maintains state on loss of power
T8
Fire1 Relay – Maintains state on loss of power
T9
Fire2 Relay – Maintains state on loss of power
T10
Minor Fault Relay – Maintains state on loss of power
T11
Urgent Relay – Always reverts to reset on loss of power
T12
Isolate Relay – Maintains state on loss of power
T13
External Monitor

SYSTEM WIRING

To maintain compliance with EN54-20, the power supply used with FAAST XT
must be EN54-4 approved. The system requires an EMI line filter in order
to meet CE certification to CISPR22 specifications. The EMI line filter (in-
cluded) needs to be connected between the DC power supply and the FAAST
device. The EMI filter needs to be located within the wiring compartment of
FIGURE 4. FACP WIRING DIAGRAM
ASP114-01
Red
Yellow (not connected)
Blue
the FAAST XT unit. Refer to Figure 4 for the proper electrical connections to
the unit. Refer to Table 1 for the field wiring terminal descriptions of the unit.
Refer to Figure 4 for a typical connection for monitoring the FAAST XT system
at a Fire Alarm Control Panel (FACP). Refer to your FACP's installation manual
for instructions on connecting FAAST XT.
SYSTEM POWERING
The following procedure describes how to initially power up the FAAST XT system.
1. Unplug the unit's power connector to the unit before turning on the power.
2. Turn on the power.
3. Check the voltage at the connector. Make sure it is within the required volt-
4. If wiring is not connected to the external monitor terminal, install a 47kΩ
3
Fire Panel (FACP) typical connection
for monitoring of device
Alarm
Short = Fire
Open = Fault
Alarm
Short = Fire
Open = Fault
FACP
Alarm
Short = Fire
Open = Fault
Alarm
Short = Fire
Open = Fault
Alarm
Short = Fire
Open = Fault
Supervisory
Short = Isolate
Open = Fault
Supervisory
Short = Urgent Fault
Open = Fault
Supervisory
Short = Minor Fault
Open = Fault
(Reset)
C.
Panel's
N.C.
47k
Remote
Reset
N.O.
EMI Line Filter
(included)
age range.
resistor (provided with the unit) into the terminal block and fit it into the T6
terminal. Remove spade connectors before installing in the wiring terminal.
FAAST XT
C.
N.C.
EOL
N.O.
C.
N.C.
EOL
N.O.
C.
N.C.
EOL
N.O.
C.
N.C.
EOL
N.O.
C.
N.C.
EOL
N.O.
C.
N.C.
EOL
N.O.
C.
N.C.
EOL
N.O.
C.
N.C.
EOL
N.O.
B.
B.
A.
Red
Blue
ASP136-01
I56-6001-001
2/5/2018

Publicidad

Tabla de contenido
loading

Tabla de contenido