QUICK REFERENCE OF PARAMETERS, ALARMS AND FAULTS
Param.
Description
P225
LOC JOG Selection
P226
REM FWD/REV Selection
P227
REM Run/Stop Selection
P228
REM JOG Selection
P229
Stop Mode Selection
P230
Dead Zone (AIs and FI1 )
(*)
P231
AI1 Signal Function
(*)
P232
AI1 Input Gain
(*)
P233
AI1 Input Signal
(*)
P234
AI1 Input Offset
(*)
P235
AI1 Input Filter
(*)
P241
Potentiometer Signal Function
(*)
P242
Potentiometer Signal Gain
(*)
P244
Potentiometer Signal Offset
P245
Potentiometer and FI1 Filter
P246
FI1 Input Function
P247
FI1 Input Gain
P248
FI1 Minimum Input
P249
FI1 Input Offset
P250
FI1 Maximum Input
8 | CFW100
Adjustable Range
0 = Disabled
1 = Not Used
2 = DIx
3 = Serial/USB
4 = Not Used
5 = CO/DN
6 = SoftPLC
See options in P223
See options in P224
See options in P225
0 = Ramp to Stop
1 = Coast to Stop
0 = Inactive
1 = Active
0 = Speed Ref.
1 to 3 = Not Used
4 = PTC
5 to 6 = Not Used
7 = PLC Use
8 = Application Function 1
9 = Application Function 2
10 = Application Function 3
11 = Application Function 4
12 = Application Function 5
13 = Application Function 6
14 = Application Function 7
15 = Application Function 8
16 = Control Setpoint
17 = Process Variable
0.000 to 9.999
0 = 0 to 10 V / 20 mA
1 = 4 to 20 mA
2 = 10 V / 20 mA to 0
3 = 20 to 4 mA
-100.0 to 100.0 %
0.00 to 16.00 s
0 = Speed Ref.
1 to 6 = Not Used
7 = SoftPLC
8 = Application Function 1
9 = Application Function 2
10 = Application Function 3
11 = Application Function 4
12 = Application Function 5
13 = Application Function 6
14 = Application Function 7
15 = Application Function 8
16 to 17 = Not Used
0.000 to 9.999
-100.0 to 100.0 %
0.00 to 16.00 s
0 = Inactive
1 = Active in DI1
2 = Active in DI2
3 = Active in DI3
4 = Active in DI4
0.000 to 9.999
1 to 3000 Hz
-100.0 to 100.0 %
1 to 3000 Hz
Factory Setting
Prop.
1
cfg
4
cfg
1
cfg
2
cfg
0
cfg
0
cfg
0
cfg
1.000
0
0.0 %
0.00 s
0
cfg
1.000
0.0 %
0.00 s
0
cfg
1.000
100 Hz
0.0 %
1000 Hz