INSTALLATION INSTRUCTIONS

- Install the oven on surfaces with adequate load-bearing
capacity.
- Safety must be the first priority. When the oven is in
operation ensure that no other fuel and materials that
may be damaged by heat and sparks are close to it.
- The outer walls of Achille may reach high temperatures
greater than 50°C.
- Position the oven so it is not in contact with the wall or
other furniture and make sure there is a gap of at least
5 cm alongside and behind the oven if you are using
fireproof materials, at least 20 cm if you do not use fire-
resistant materials.
- The upper part of the appliance can not be recessed
and must remain free from furniture that compromise
EN
the correct ventilation.
- The accessory works must not rest on the structure of
the oven.
- Do not move the oven while it is in use.
1. VENTILATION
The A1 appliances must be installed in well-ventilated
areas to prevent concentration of substances hazardous to
health in the room.
1.1 Natural ventilation
Natural ventilation can be obtained by using one or more
permanent openings on walls/windows/fixtures or through
ventilation ducts. The net area of the ventilation openings
must be no less than 6 cm2/kW with a minimum of 100
cm2; in the presence of ventilation ducts, they must have
a cross-section of not less than 9 cm2/kW with a minimum
of 150 cm2. The ventilation apertures may be made in the
walls, on the doors or on the window systems of the room
or the combustion air room facing outwards; they can
be obtained by increasing the gap between doors facing
outwards and the floor of the room or the combustion
air room or they can be realized on the fixtures facing
outwards as long as the free air flow is guaranteed and
the net cross-section is measurable. The ventilation of
the room can also be implemented by an individual or collective ventilation duct provided that this pipework is
impermeable to smoke and gas with neither change in direction nor sharp edges. In case of indirect ventilation
of the room where the gas appliance is installed, the circulation of air between adjacent rooms may be ensured
thanks to several air flow openings as long as each of them has a net cross-section area of not less than 6 cm2/
kW and provided that the sum of the net cross-sections of the openings is not less than the calculated net useful
cross-section of 6 cm2/kW. Such apertures can be made in the walls or in the doors of the common walls or can
be obtained by increasing the gap between the inner doors and the floor of the premises as long as the free air
flow is guaranteed and the net cross-section is measurable.
18