OPTIMA / MAYA SERIES · BOMBA DE CALOR AIRE/AGUA
HEATING ON(F37=0)
10S
water pump on
15S
FAN on
F21(1~3min)
COMP1 on
F21+30s
COMP2 on
HEATING ON(F37=1)
0S
4-way valve on
10S
water pump on
15S
FAN on
F21(1~3min)
COMP1 on
F21+30s
COMP2 on
6.4.3 MODO ENFRIAMIENTO (SOLO DISPONIBLE EN MODELOS
Proceso de arranque:
Condiciones de arranque : Temperatura de entrada del agua < (Temperatura de
consigna+ Diferencial de temperatura); y el Tiempo de parada compresor ≥ Tiempo de
retardo compresor.
ON(F37=1)
COOLING
10S
water pump on
15S
FAN on
F21(1~3min)
COMP1 on
F21+30s
COMP2 on
ON(F37=0)
COOLING
0S
4-way valve on
10S
water pump on
15S
FAN on
F21(1~3min)
COMP1 on
F21+30s
COMP2 on
© FLUIDRA 2019 ALL RIGHTS RESERVED. PROPRIETARY DOCUMENT.
0S
5S
20s
F42
0S
5S
20s
50s
F42
CHILLER)
0S
5S
20s
F42
0S
5S
20s
50s
F42
ESPAÑOL
HEATING OFF(F37=0)
COMP1 off
COMP2 off
FAN off
water pump off
HEATING OFF(F37=1)
COMP1 off
COMP2 off
FAN off
4-way valve off
water pump off
OFF(F37=1)
COOLING
COMP1 off
COMP2 off
FAN off
water pump off
OFF(F37=0)
COOLING
COMP1 off
COMP2 off
FAN off
4-way valve off
water pump off
Pag: 24