DPX
630 and 1600
3
common auxiliaries
4 222 42
4 222 48
Auxiliary contact or fault signal
Pack
Cat.Nos
1
4 210 11 For signalling the state of the contacts
or opening of the MCCB on a fault
For DPX³/DPX³-I
Changeover switch 3 A - 240 V±
Shunt releases
Allow remote tripping of a DPX
DPX3-I 630 and DPX
Shunt inrush power 300 VA
4 222 39 Coil voltage 24 V± / =
1
4 222 40 Coil voltage 48 V± / =
1
4 222 41 Coil voltage 110 V± / =
1
4 222 42 Coil voltage 230 V± / =
1
4 222 43 Coil voltage 400 V± / =
1
Undervoltage releases
Allow remote tripping of a DPX
DPX
-I 630 and 1600
3
Consumption: 5 VA
1
4 222 44 Coil voltage 24 V=
1
4 222 45 Coil voltage 24 V±
4 222 46 Coil voltage 48 V=
1
1
4 222 47 Coil voltage 110 - 125 V±
4 222 48 Coil voltage 220 - 240 V±
1
1
4 222 49 Coil voltage 380 - 415 V±
Time-lag (800 ms) undervoltage release
Allow remote tripping of a DPX
Prevents false tripping in the event of power supply
microbreaks
Time-lag modules
1
0 261 90 230 V±
1
0 261 91 400 V±
Release
To be equipped with a time-lag
module Cat.Nos 0 261 90/91
4 226 23
For DPX
/DPX
1
3
Automation control units
for supply invertors p. 157
Power supervision system
p. 97
146
or
3
1600
3
3
or
/DPX
-I 630 or 1600
3
3
Number of modules
3
3
-I 630 and 1600
3
DPX
160, 250, 630 and 1600
3
power supervision system
0 261 78
Auxiliary power supply for DPX
Pack
Cat.Nos
For supplying DPX
breaker is open or when the current passing through
it is insufficient
4 210 83 Input voltage 24 V± / =
1
2 modules
Output 250 mA: can supply several circuit breakers
Consumption:
- Thermal-magnetic DPX³ with residual current
protection: 42 mA
- Electronic DPX
- Electronic DPX
- Electronic DPX
54 mA
- Electronic DPX
and measurement: 54 mA
RS485 Modbus communication interface
DPX
electronic interface
3
1
4 210 75 For connecting electronic DPX³ (except DPX³ 630
and 1600 S1 electronic releases) to an RS485
Modbus communication network
All the information managed by the circuit breaker's
electronic card will be shared on the Modbus
network
Dimension: 2 modules
Power supply: 24 V± / =
RS 485 link (2-wire)
Address, speed and coding can be modified with
configurator kit
Modular power supply
0 035 67 230 V± - 27 V= - 0.6 A
2 modules
Remote communication and supervision
Energy management multi-support web servers
Allow remote configuration, test, control and
visualization, via a web browser on PCs,
smartphones, web viewers, tablet computers, of
data collected from: protection devices (DX
modules with integrated measurement control unit,
DPX
and DMX
3
multi-function measuring units and CX
management system
1
0 261 78 For 32 Modbus adresses or 32 pulse modules
1
0 261 79 For 255 Modbus adresses or 32 pulse modules
Legrand Software dedicated to measurement
For displaying the values collected from electricity
meters or multi-function measuring units on a PC
connected to the network
1
0 261 88 For 32 metering devices (supplied on CD)
1
0 261 89 For 255 metering devices (supplied on CD)
Door mounting touch screen
0 261 56 Optional touch screen allowing to:
1
- visualize information coming from DX
DMX
protection devices and EMDX
3
measuring units and
- control protection devices equipped with the
universal control module Cat.No 4 149 32 (p. 92)
Can manage up to 9 devices
Power supply: 18-30 V =
IP connection
For mounting on door or solid faceplate
Door cut: 92 x 92 mm
0 261 56
3
electronic units when the circuit
3
: 30 mA
3
with measurement: 54 mA
3
with residual current protection:
3
with residual current protection
3
3
), EMDX
electricity meters and
3
3
3
energy
, DPX
3
multi-function
3
add-on
and
3