5.5.1.4 Examples
examples of settings:
DS-8 AC-in-1
on
DS-7 AC-in-1
on
DS-6 AC-in-1
on
DS-5 AC-in-2
on
DS-4 Charging current
on
DS-3 Charging current
DS-2 Stand-alone mode
DS-1 Stand-alone mode
Step1, stand-alone
Example 1 (factory setting):
8, 7, 6 AC-in-1: 50A
5 AC-in-2: 30A
4, 3 Charge current: 75%
2, 1 Stand-alone mode
To store the settings after the required values have been set: press the 'Up' button for 2 seconds (upper button to the right of
the DIP switches, see appendix A, position K). The overload and low-battery LED's will flash to indicate acceptance of the
settings.
We recommend making a note of the settings, and filing this information in a safe place.
The DIP switches can now be used to apply the remaining settings (step 2).
5.5.2 Step 2: Other settings
The remaining settings are not relevant for slaves.
Some of the remaining settings are not relevant for followers (L2, L3). These settings are imposed on the whole system by the
leader L1. If a setting is irrelevant for L2, L3 devices, this is mentioned explicitly.
ds8-ds7: Setting charging voltages (not relevant for L2, L3)
Absorption
Float
ds8-ds7
voltage
oltage
14.1
13.8
off
off
28.2
27.6
56.4
55.2
14.4
13.8
off
on
28.8
27.6
57.6
55.2
14.7
13.8
on
off
29.4
27.6
58.8
55.2
15.0
13.8
on
on
30.0
27.6
60.0
55.2
ds6: absorption time 8 or 4 hours (not relevant for L2, L3)
ds5: adaptive charging characteristic (not relevant for L2, L3)
ds4: dynamic current limiter
ds3: UPS function
ds2: converter voltage
ds1: converter frequency (not relevant for L2, L3)
(the wide input frequency range (45-55Hz) is 'on' by default)
Note:
-
If "adaptive charging algorithm" is on, ds6 sets the maximum absorption time to 8 hours or 4 hours.
-
If "adaptive charging algorithm" is off, the absorption time is set to 8 hours or 4 hours (fixed) by ds6.
18
DS-8
on
DS-7
on
DS-6
on
DS-5
off
DS-4
on
DS-3
on
off
DS-2
off
off
DS-1
off
off
Step1, stand-alone
Example 2:
8, 7, 6 AC-in-1: 50A
5 AC-in-2: 16A
4, 3 Charge: 100%
2, 1 Stand-alone
Storage
Suitable for
voltage
13.2
Gel Victron Long Life (OPzV)
26.4
Gel Exide A600 (OPzV)
52.8
Gel MK battery
Gel Victron Deep Discharge
13.2
Gel Exide A200
26.4
AGM Victron Deep Discharge
52.8
Stationary tubular plate (OPzS)
AGM Victron Deep Discharge
13.2
Tubular plate (OPzS) batteries in
26.4
semi-float mode
52.8
AGM spiral cell
13.2
Tubular plate (OPzS) batteries in
26.4
cyclic mode
52.8
DS-8
off
DS-7
on
DS-6
on
DS-5
off
DS-4
on
DS-3
on
DS-2
off
DS-1
off
Step1, stand-alone
Example 3:
8, 7, 6 AC-in-1: 16A
5 AC-in-2: 16A
4, 3 Charge: 100%
2, 1 Stand-alone
on = 8 hours
off = 4 hours
on = active
off = inactive (fixed absorption time)
on = active
off = inactive
on = active
off = inactive
on = 230V
off = 240V
on = 50Hz
off = 60Hz
DS-8
on
DS-7
on
DS-6
off
DS-5
on
DS-4
off
DS-3
on
DS-2
off
DS-1
off
Step1, stand-alone
Example 4:
8, 7, 6 AC-in-1: 30A
5 AC-in-2: 30A
4, 3 Charge: 50%
2, 1 Stand-alone