Types Of Installation; Electrical Connection - Ferroli AT 18 Manual De Instalación, Uso Y Mantenimiento

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

2.4 Fume exhaust
The fumes can be exhausted through a connection to a conventional flue or an external duct with double wall or
insulated pipe.The fume exhaust connections must guarantee a minimum draught of 10 Pa so that the evacuation of
fumes is assured in case of a temporary power failure.
- The installer must check the efficiency and state of the flue and its conformity with the local, national and European
regulations.
- Certified pipes and connections with adequate seals guaranteeing their tightness must be used.
- In case of fire, shut down the stove, promptly call the fire department, and avoid continual attempts to extinguish it.
- Clean the flue and respective connection at least once a year.

2.4.1 Types of installation

Listed below are definitions and requirements for correct installation of an
exhaust flue in accordance with Italian Standard UNI10683:
FLUE : a vertical duct for collecting and expelling, at an appropriate height
from ground, the fumes coming from a single unit and, where permitted,
more than than one.
FLUE technical requirements :- it must be fumetight, isolated and insulated
depending on its use;
- it must have a mainly vertical path with axis deviation < 45°;
- it must be at a suitable distance from flammable materials with insulation
or air gap;
- it must preferably have a constant, free and independent round internal
section;
- it is advisable for the flue to have an inspectionable chamber for the
collection of solid materials
- and any condensate, placed under the beginning of the fume duct.
FLUE CONNECTION or DUCT: duct or connection element between the
unit and flue for evacuation of fumes.
DUCT technical requirements: - it must not cross rooms in which the installation of combustion units is not allowed;
- flexible metal tubes or fibre cement pipes are prohibited;
- the use of counter-sloping elements is prohibited;
- horizontal sections must have an upward slope of at least 3°;
- the length of the horizontal section must be minimal and not more than 3 m;
- there must not be more than 3 changes of direction, without the T union;
- with change of direction > 90° a max. of 2 bends can be used with length in horizontal projection not exceeding 2 m
- the fume duct must have a constant section and allow the recovery of soot.
CHIMNEY CAP: a device placed on the top of the flue to facilitate the dispersion of fumes into the
atmosphere.
CHIMNEY CAP technical requirements: - it must have a section equivalent to that of the flue;
- it must have a useful section not less than double the internal section of the flue;
- it must prevent the entry of rain and foreign bodies and ensure the discharge of fumes in any
atmospheric condition;
- it must ensure an adequate dilution of fumes and be positioned outside the backflow area;
- it must be without mechanical means of suction.
The
direct
( even open air ).
2.5 Turbulator and baffle position check
Before lighting the stove make sure the brazier is in the correct position, i.e. fitted in the special slots. Also make
sure the turbulator shaker device is resting in a lower position. An incorrect position of the brazier and/or turbulators
can result in malfunctioning and excessive blackening of the glass.
At every stove lighting check the correct position of the brazier and turbulator shaker device.

2.6 Electrical connection

Connect one end of the power cable to the rear socket of the stove, and the other to the wall socket.
The voltage supplied by the system must match that specified on the stove dataplate and in the technical data
section of this manual.
Plug the device power cord must be connected only AFTER the end of the installation and assembly of the device
and must remain accessible. During stove idle periods it is advisable to remove the power cable.
Make sure the electrical system is equipped with an earth and differential switch in accordance with the current
Regulations.
The power cable must never touch the stove exhaust pipe.
discharge
of
fumes
must
Min. distance 0.2 m
take
place
on
the
roof
39
Comignolo
Antiwind
antivento
grille
Canna
Flue
fumaria
Camera
ispezionabile
Distanza min 0.2m
and
not
towards
closed
Flue
Raccordo
connection
fumi
Inspectionable
chamber
Presa d'aria
Ext. air inlet
esterna
min.100 cm 2
2
min.100 cm
spaces
AT 18

Publicidad

Tabla de contenido
loading

Tabla de contenido