Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Controls

Other than a Manual Override lever, there are no operator controls
because this is an automatic transfer switch. The manual override
is to be used only by licensed professionals. Information on handle
use can be obtained by calling Technical Service at 800-743-4115.
Operation
To select automatic transfer operation, do the following:
1. In transfer switch, set utility disconnect circuit breaker
to "ON" position.
2. In transfer switch, set generator disconnect circuit
breaker to "ON" position.
3. Install 15 Amp fuse in generator's control panel.
4. Set generator's circuit breaker to "ON" position.
5. Set generator's system switch to "AUTO" position.
The system will now be in automatic operation mode.
When the generator is providing power to the transfer
switch, the transfer switch control board is constantly
monitoring generator power. If the air conditioner is called
to run, and there is sufficient generator power available,
the controller will close contacts "A-A" to air conditioner
contactor. Contacts "B B" will open before contacts A-A
close. If loads are too great for the generator, contacts A-A
and/or B-B will open. When air conditioning is not needed,
A-A will open. If enough power is available, B-B will close.
Enclosure Door
To open door, press the spring-load door lock to the right
and pull down on the door.
To close and latch door, push door closed against enclosure.
While in this position, push door upwards. This will cause
spring-load door lock to engage and latch door in place.
Enclosure door MUST be closed and latched at all times
except when system is being serviced.
7

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

071044071046071069

Tabla de contenido