System Operation; Testing The Automatic Transfer Switch; Automatic Sequence; Utility Fail - Briggs & Stratton 01813-1 Manual De Instalación Y Del Operario

Tabla de contenido

Publicidad

Briggs & Stratton Generac Generator Discount Parts Call 606-678-9623 or 606-561-4983

SYSTEM OPERATION

To select automatic transfer operation, do the following:
1A. For models 01813-1 & 01814-1, set service disconnect
switch that sends utility power to transfer switch
contactor to "On" position.
B. For models 01928-1 & 01929-1, set service disconnect
switch that sends utility power to transfer switch utility
disconnect circuit breaker to "On" position.
2.
For models 01928-1 & 01929-1, set transfer switch
utility disconnect circuit breaker to "On" position.
3.
Set generator's main circuit breaker to its "On"
position.
4.
Install 15 Amp fuse in control panel on generator.
5A. If generator is equipped with a system ON/OFF
switch, set switch to "On" position.
B. If generator is equipped with a AUTO/OFF/MANUAL
switch, set switch to "AUTO" position.
The system will now be in automatic operation mode.
TESTING THE
AUTOMATIC TRANSFER
SWITCH
Turn the service disconnect feeding the transfer switch, to
the "Off" position.The automatic sequence will follow.To
go back to utility power, turn the service disconnect to the
"On" position.
Briggs & Stratton Power Products Automatic Transfer Switch
Installation and Operator's Manual
www.mymowerparts.com

Automatic Sequence

Utility Fail

The Home Standby Generator set senses when utility
voltage is below 70 percent of nominal. Engine start
sequence is initiated after 6 second time delay.

Engine Warm-Up

Time delay to allow for engine warm-up before transfer
fixed at 20 seconds or 50 seconds with removal of jumper
on control board.

Transfer

Transfer from utility to standby supply occurs after standby
voltage is above set levels. Minimum engine run time is
5 minutes after transfer.

Utility Pickup

Voltage pickup level is 80 percent of nominal voltage.

Retransfer

Retransfer from standby to utility supply is approximately
10 seconds after utility voltage supply is above pickup level
and minimum run time is completed.

Engine Cool Down

Engine will run for 60 seconds after retransfer.

When Calling the Factory

Before contacting Briggs and Stratton Power Products
regarding service or repair of this transfer switch, obtain
the Model Number and Serial Number from the unit data
decal located on or inside the case.
To contact Briggs and Stratton Power Products call
1-800-743-4115, between 8:00 AM and 5:00 PM CT.
10

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

01814-101928-101929-1

Tabla de contenido